Figure 21: Push buttons
[1]
Set end position OPEN
push button
[2]
Set operation in direction OPEN push button
[3]
Set operation in direction CLOSE push button
[4]
Set end position CLOSED
push button
[5]
LED
Risk of passing set end positions!
→
During operation in directions OPEN/CLOSE, the actuator stops when reaching
the set end position. When pressing again the button, the actuator runs until
reaching a mechanical stop (end stop of the actuator or the valve) or passes
the end position when releasing the button.
1.
Run actuator in direction OPEN: Hold down button [2].
➥
The LED flashes in green during operation in direction OPEN.
2.
Run actuator in direction CLOSE: Hold down button [3].
➥
The LED flashes in red during operation in direction CLOSE.
8.2.2.
Actuator operation via AUMA Assistant App
Functions
Alternatively, actuator operation is possible using the “AUMA Assistant” smartphone
App. The following table shows an overview of the menus of the AUMA Assistant
App and the AUMA CDT software.
Description
Menu
Display of all available warnings and faults including
respective details.
Actuator diagnostics and detailed diagnostics
Diagnostics
Operation in direction of end positions
Resetting the fault log
Operation function
Setting the positions for end positions CLOSED and
OPEN
Setting end positions
Device designation
Order number, serial number
Device ID
Configuration of all parameters
Configuration
Factory settings
Rebooting the actuator
Service functions
32
PF-M25X – PF-M100X
Operation
Parallel