6.
Electrical connection
6.1.
Basic information
Electric shock due to presence of hazardous voltage!
Risk of death or serious injury!
→
The electrical connection must be carried out exclusively by suitably qualified
personnel.
→
Prior to connection, observe basic information contained in this chapter.
Risk of immediate actuator operation when connecting to mains!
Risk of death, severe injury or damage to valve.
→
Check operation signals and operation behaviour prior to switching on the mains
voltage.
→
Ensure that the tripping conditions for the failure behaviour are not fulfilled when
switching on.
→
Ensure that the tripping conditions for the EMERGENCY behaviour are not ful-
filled when switching on.
Reasons for immediate operation:
●
The signal and fieldbus cables are connected and a respective operation com-
mand has been issued.
●
The “Failure behaviour” function was configured as to ensure that this state
results in an operation once the mains voltage is applied. Factory setting para-
meter
Failure operation
: STOP (the actuator stops).
●
The “EMERGENCY behaviour” function was configured as to ensure that this
state results in an operation once the mains voltage is applied. Factory setting
function
EMERGENCY behaviour
: Function not activated.
Wiring diagram/terminal
plan
The pertaining wiring diagram/terminal plan (in German or English) is attached to
the device in a weather-proof bag, together with these operation instructions. It can
also be requested from AUMA (state order number, refer to name plate) or
downloaded directly from the Internet (http://www.auma.com).
Permissible networks
(supply networks)
The actuators are suitable for use in TN and TT networks. For IT network, a suitable,
approved insulation monitor measuring the pulse code is required.
Current type, mains
voltage, mains fre-
quency
Type of current, mains voltage and mains frequency must match the data on the
name plate.
For short-circuit protection and for disconnecting the actuator from the mains, fuses
and disconnect switches or circuit breakers have to be provided by the customer.
For circuit breakers, the following sizing/characteristics are recommended:
Sizing/
characteristics
Number of actuators
B06
1
B10
2
C13
4
D16
10
Refer to electric data for the maximum current values of individual models and
versions.
Potential of customer
connections
Refer to Technical data for options of isolated potentials.
17
PF-M25X – PF-M100X
Parallel
Electrical connection