Close timer start Valve Position : The user has to set the valve position at which this Timer
mode should go on for Close command.
Close ON time : This parameter decides the amount of time (in s) the actuator runs in Close
direction before shutting off for Close OFF time (in s). This continues to happen until the
respective limit switch is hit (unless the switch is bypassed).
Close OFF time : This parameter decides the amount of time (in s) the actuator shuts off
before running in open direction for Open ON time (in s). This continues to happen until the
respective limit switch is hit (unless the switch is bypassed).
2.12
PROGRAMMABLE RELAYS
As per standard two relays are given for customer end information - Fault Relay & Optional Relay 1.
There are about 6-8 more additional relays that have been added along with this module. Each of
these relays can be configured for the following 27 faults/statues as given below.
List of available relays
o Fault Relay
o Optional Relay ( 3 relays)
o Additional Relay(2 Latching relays)
Available Programmable options are:
o
Opened (Open Limit Trip)
o
Closed (Close Limit Trip)
o
Remote Local stop
o
Local Stop
o
Open Torque Trip
o
Close Torque Trip
o
Loss of Phase
o
TH-Trip
o
TOLR Trip
o
Control Supply Fail
o
Phase reversal
o
Jammed Valve
o
Power ON
o
Program Mode Indication
o
SP Reached ( via DAC/MODBUS)
o
Selector SW LOCAL
o
Selector SW OFF
o
Selector SW REMOTE
o
ESD Pressed
o
24V DC Fail
o
Space Heater Fail
o
Running Open
o
Running Close
o
Remote Selector SW EN
o
PVST Fail
o
Intermediate Pos
o
4-20mA Signal Fail
2.13
REAL TIME CLOCK (RTC)
This module has a Real time clock that is used to obtain the time-stamp for Event logging. The RTC
can be configured by Auma Utility Software or by manually setting the RTC in Program Mode
settings. The RTC is powered by a Super Capacitor when the power is off which is another added
feature of this module. The Super Capacitor takes about 2 hours to charge and can supply power