Required user level:
Specialist (4)
or higher.
Customer settings M0041
Interlock M0664
Running dir. Interlock M0666
Default value:
OPEN and CLOSE
Setting values:
OPEN
The enable signal is only required for operation commands in direction OPEN.
CLOSE
The enable signal is only required for operation commands in direction CLOSE.
OPEN and CLOSE
The enable signal is required for operation commands in directions OPEN and
CLOSE.
9.7.
Local Stop
Properties
●
The function Local Stop can be used to stop an operation from Remote locally
with the push button STOP.
●
All operation commands are interrupted.
Information
After releasing push button STOP, an operation command which might still be present
will become active immediately.
9.7.1.
Behaviour
Required user level:
Specialist (4)
or higher.
Customer settings M0041
Local controls M0075
Local STOP M0627
Default value:
Off
Setting values:
Off
Push button STOP can only interrupt an operation in operation mode
Local
(selector
switch = position Local control).
Sel.sw.Local + Remote
In the operation modes
Local
,
Remote
,
Remote II
,
EMERGENCY
and
Service
, push
button STOP interrupts an operation.
Information
In operation mode
Disabled
, an interruption is NOT possible.
9.8.
EMERGENCY stop function
Conditions
An EMERGENCY stop button (latching) is either located on the electrical connection
or outside.
Characteristics
●
In an emergency, the EMERGENCY stop button can be used to interrupt the
power supply. Possibly available operation commands will be reset via self-re-
taining.
●
The indication in the top row of the display shows:
EMCY stop
97
Actuator controls
ACV 01.2/ACVExC 01.2 Profibus DP
Failure functions