9.9.7.
PVST operating time: set
During operating time controlled PVST execution (parameter
PVST operation mode
M0889
=
End position test
), this parameter determines the permissible PVST
operating time.
Customer settings M0041
PVST M0852
PVST operating time M0890
Default value:
00:02.0 min:s
(2 seconds)
Setting range:
00:00.1 ... 15:00.0 min:s
(minutes:seconds)
9.9.8.
PVST reversing time: set
Waiting time during PVST prior to returning to initial position.
Customer settings M0041
PVST M0852
PVST reversing time M0891
Default value:
00:02.0 min:s
(2 seconds)
Setting range:
00:00.1 ... 15:00.0 min:s
(minutes:seconds)
9.9.9.
PVST reminder
If this function is active, a signal is generated if no PVST was executed during the
reminder period.
Activate reminder
Required user level:
Specialist (4)
or higher.
Customer settings M0041
PVST M0852
PVST reminder M0892
Default value:
Function not active
Setting values:
Function not active
Reminder not activated.
Function active
Reminder activated.
Set reminder period
Customer settings M0041
PVST M0852
PVST reminder period M0893
Default value:
0 d
Setting range:
0 ... 65535 d
(days)
9.9.10.
Speed for PVST: set
The speed during PVST may be set individually for both directions (OPEN/CLOSE).
Required user level:
Specialist (4)
or higher.
Customer settings M0041
PVST M0852
Speed PVST Open M2056
Speed PVST Close M2057
Default value:
45 rpm
Setting ranges:
6 ... 240 rpm
101
Actuator controls
ACV 01.2/ACVExC 01.2 Profibus DP
Failure functions