background image

MANUAL

 

HTi

70

 6 & 8 KW HEAT PUMPS 

-

27

NOTES / MAINTENANCE

Date

Technician 

 

                      Work carried out

Refrigerant collected

Refrigerant loaded

Summary of Contents for 955000

Page 1: ...al HTi70 High temperature ultra modulating Heat pump HTi70 6 Ref 955000 HTi70 8 Ref 955010 The information contained in this document is non contractual The manufacturer reserves the right to modify any technical specifications and equipment of any appliances without prior notice ...

Page 2: ...eneral information 14 6 2 Maintenance on the hydraulic circuit 14 6 3 Maintenance of the Heat pump 14 6 4 Maintenance of the electrical components 14 6 5 Consulting the meters 14 6 6 Sensor data curve charts 15 6 6 1 Waterinletandoutlet de icingsensor airintakesensor sensorsinstalledon compressors1and2 15 6 7 Modification 15 6 8 Decommissioning 15 6 8 1 Interim Decommissioning of Product 15 6 8 2 F...

Page 3: ...e that there is no possibility of the power supply becoming active again Wait at least 5 minutes for the capacitors to lose their charge Do not get water on any of the control or electrical components Always disconnect the appliance from the electricity supply before carrying out work on any of the electrical components Danger of death if the pressure relief valves are missing or defective A defec...

Page 4: ...ease of refrigerant fluid into the atmosphere is prohibited the refrigerant fluid must be recovered before any work is undertaken on the refrigerant circuit The Heat pump uses R290 refrigerant fluid Given the flammable nature of the fluid any work on the refrigerant circuit must be done with appropriate materials and by conforming to all regulations in effect In case of handling of fluid recovery ev...

Page 5: ...t Admissible storage and transport temperatures of the appliance are between 20 C and 60 C The appliance must be stored in a room that does not contain sources of ignition that are continuously operating for example bare fires gas appliance or electric radiator in operation 3 2 1 General information The appliances must be stored and transported packaged and on their wooden pallets in a vertical pos...

Page 6: ...nlet outlet 7 Condensates drainage ItisFORBIDDEN tooperatetheHeatpumpusingair intakecontainingsolventsorexplosive materials touseairintakecontaining grease dust or aerosolparticles toconnectventedexhausthoodstothe appliance UseoftheappliancesareFORBIDDEN if theinstallationisnotfilledwithwater àExternal defrost kit Réf 754101 to keep the external condensate evacuation duct from freezing àHydraulic k...

Page 7: ...s this can result in a mixture of oil and air settling onto the heat exchanger fins which could hamper its performance Inanareawithflammablegaz acidicsubstances oralkalineswhichcouldcauseirreversible damagetothecopper aluminiumheat exchanger PROHIBITED INSTALLATION AvoidinstallingtheHeatpumpina locationsubjecttonoisereverberationsuch asnearwindowsornearthecornersofbuildings Asthecondensatesdrainingt...

Page 8: ...tilated shelter with a large enough opening to allow sufficient air flow for intake and exhaust Placed on the ground or on a terrace empty area Placed against a wall 3dB A Placed in a yard 9dB A Placed in a corner 6dB A 5 2 2 Minimum distances for placement Minimum distances to be respected for the placement of the Heat pump 30cm 1m 1m 30cm 30cm 2m 5 2 1 Accepted installation sites Neighbouring home ...

Page 9: ...s attached in the documentation pouch 5 3 1 Condensates drainage When the appliance is operating in frost protection mode the condensed water must be drained off In order for the condensates to drain properly the drainage trough and hole must be clean and free of all debris leaves grass etc If the condensates drainage pipe is connected to the rainwater run off system it is advised to use a siphon Do...

Page 10: ...t2 5bars Aservice pressurebelowthisvalueshouldbemaintained 5 4 1 Hydraulic connections on the installation 5 4 Hydraulic installation In order to ensure that fluids can circulate properly it is advisable to check that the sizing of piping in the circuit is appropriate between the Heat Pump and the Pilot 1 Hydraulic pilot 2 Heat pump 3 Pressure relief valve G 1 M set at 2 5 bars 4 Filter valve G 1 M...

Page 11: ...30m of load loss 22 24 22 24 If distance between HP and pilot 10m and 15m the equivalent of linear 20m of load loss 24 26 24 26 If distance between HP and pilot 15m and 25m the equivalent of linear 50m of load loss 28 30 28 30 If distance between HP and pilot 25m and 50m the equivalent of linear 100m of load loss 32 34 32 34 5 5 Connecting to the power supply Therulesandregulationsinthecountryof i...

Page 12: ...ssional to avoid any risk of danger To access the terminals remove the panel on the right hand side 2 screws and the front panel 4 screws and open the electrical box 4 screws 1 Theinformationgivenhereisforinformationpurposesonly Itmustbeverifiedandadaptedifneededbased on the installation conditions and on the standards in effect If cable length exceeds 15m or if the network is subject to drops in vo...

Page 13: ...n the heat pump and the pilot 1 Hydraulic pilot 2 Bus cable Colour of wire A Brown B White GND Black Phase Fuse or thermical magnetic circuit breaker Power supply 230V 50Hz Ground Ground Neutral Phase Neutral See Recommendations for conection the system to the power supply ...

Page 14: ...with water Nevercleanthefinnedheatexchanger withhigh pressurecleaningequipment asitcoulddamagethefins 6 3 MaintenanceoftheHeatpump Alwaysdisconnecttheappliancefrom thepowersupplybeforeaccessingthe electricalterminals Donotgetwateronanyoftheelectrical components 6 4 Maintenanceoftheelectrical components Check on both the HTi70 Heat pump and the HTi70 Pilot that the electrical supply cables are proper...

Page 15: ...0 1 2 3 4 5 6 7 8 9 10 11 12 20 30 40 50 60 70 80 90 C k 6 7 Modification Any modification of the device is prohibited Any replacement of components must be done by a professional with original parts from the manufacturer 6 8 Decommissioning In the event of a prolonged absence with a power cut to the housing and product ask a qualified professional to drain the product or protect it from freezing 6 8...

Page 16: ...or 13 4994697 4997697 Ventilator spiral 14 1244833 1244833 Water inlet temperature sensor 15 1244577 1244577 Water outlet temperature sensor 16 1244522 1244522 Air temperature sensor 17 1244834 1244834 Compressor temperature sensor 18 1239128 1239128 Pressure relief valve 2 5 bars 19 4994309 4994309 Cover kit 20 1657757 1657757 Compressor insulation 21 1244856 1244856 HP C9 circuit board 22 124459...

Page 17: ...e collapse or settling of the ground or the structure where the appliance is installed Any other damage which is not due to defects in the product We do not guarantee against variations in the colour of the appliance or damage caused by air pollution exposure to chemical elements or changes brought about by adverse weather conditions The products are not guaranteed against dirt rust grease or stai...

Page 18: ...6 00 6 00 6 00 Nominal heat ouput 2 90 2 95 2 92 2 94 COP 5 67 4 03 3 08 2 40 MAX heat ouput 7 C 6 00 6 00 6 00 6 00 Nominal heat ouput 4 17 4 22 4 27 4 19 COP 5 05 3 76 3 04 2 38 MAX heat ouput 2 C 6 00 6 00 6 00 6 00 Nominal heat ouput 4 57 4 51 4 56 4 58 COP 3 97 3 17 2 63 2 19 MAX heat ouput 7 C 6 00 6 00 5 70 5 50 Nominal heat ouput 4 93 5 16 5 11 5 33 COP 2 98 2 58 2 19 1 92 MAX heat ouput 1...

Page 19: ...n withoutmeasuringthepHtocheckthatthe dropinglycol isnotduetoadeteriorationof theglycol WhenthepHisacidic 7 replaceallofthe glycolafterhavingalreadydrainedandrinsed theinstallation A4 Treatment of the water in the heating circuit A4 1 Preparingthehydrauliccircuit rinsing Before installing the Pilot and the HTi Heat Pump it is necessary to rinse the installation with an appropriate product This per...

Page 20: ...lear with no traces of impurities left Protect the installation against corrosion with a corrosion inhibitor example SENTINEL X100 Or against corrosion and freezing with an inhibitor with an anti freeze additive Example SENTINEL X500 or SENTINEL R600 Corrosion inhibitor protects against the formation of limescale prevents pinhole type corrosion prevents in new installations the formation of sludge...

Page 21: ... MANUAL HTi70 6 8 KW HEAT PUMPS 21 A5 2 HTi70 8 kW Heat pump 1 Heat pump outlet 2 Heat pump inlet 3 Communication bus 4 Electrical supply ...

Page 22: ...sonal energy efficiency 3 ηs Puissance sonore extérieure Sound power level outdoor LWA Consommation annuelle d énergie Annual energy consumption 3 QHE efficacité énergétique saisonnière Seasonal energy efficiency 2 ηs Tj 7 C 4 Pdh Tj 12 C 4 Pdh Tj 7 C 4 Pdh Tj 2 C 4 Pdh Tj 15 C 4 Pdh Température bivalente Bivalence temperature Tbiv Tj température bivalente Tj Bivalence temperature 4 Pdh Tj tempéra...

Page 23: ...ure limite fonctionnement Tj Operating limit value temperature 5 COPd Tj 7 C 5 COPd Tj 12 C 5 COPd Tj 15 C 4 Pdh Température bivalente Bivalence temperature Tbiv Tj température bivalente Tj Bivalence temperature 4 Pdh Tj température limite fonctionnement Tj Operating limit temperature 4 Pdh Tj 7 C 5 COPd Puissance sonore extérieure Sound power level outdoor LWA Consommation annuelle d énergie Annu...

Page 24: ... MANUAL HTi70 6 8 KW HEAT PUMPS 24 A7 Internal wiring diagram ...

Page 25: ...r Tévap Condenser outlet temperature sensor Tair Air intake temperature sensor TCP1 Compressor 1 temperature sensor HP High pressure sensor LP Low pressure sensor HP1 Compressor 1 high pressure switch F1 Fuse 5x20 4A F2 Fuse 10x38 20A EV Defrosting solenoid valve CC Condensate drain pan defrost heating cord ...

Page 26: ... MANUAL HTi70 6 8 KW HEAT PUMPS 26 NOTES MAINTENANCE Date Technician Work carried out Refrigerant collected Refrigerant loaded ...

Page 27: ... MANUAL HTi70 6 8 KW HEAT PUMPS 27 NOTES MAINTENANCE Date Technician Work carried out Refrigerant collected Refrigerant loaded ...

Page 28: ... de la République CS 40029 80210 Feuquières en Vimeu Spare Parts Department Tel 03 22 61 21 21 Fax 03 22 61 33 35 E mail pieces auer fr Technical Assistance Department E mail enr auer fr Technical assistance is reserved for professionals ...

Reviews: