6.9.2 - Operating in case of error
Display
Name
Source of defect
Consequence(s)
Repair & removing
error message
AIR HP
ERR
Air temperature
sensor defect
HP air temp. sensor data is illogical
Target temperature =
(max.water temp.+ min. water temp) / 2
Automatic
after repair
AMBIeNCE 1
ERR
Amb1 sensor
defect
Attention : the room temperature sensor
with display should be entered as INT
SENSOR for circuit 1 only
• Room temperature control for circuit 1
is programmed in just as SENSOR
and the data received is illogical
or
• It is not, so the swimming pool sensor
is recognised and the data received
is illogical
Heating request
Automatic
after repair
AMBIENCE 2
ERR
Amb 2 sensor
defect
Attention : the room temperature sensor
with display should be entered as INT
SENSOR for circuit 1 only
Circuit 2 is programmed as a radiator or
underfloor heating circuit with room
temperature sensor and the data received is
illogical
Heating request
Automatic
after repair
BUS
err
BUS
2-core sheathed cable
or BUS connector defect
or fuse not working
or electronics board(s) defect
HP stopped, back-up
only authorised
BUS link
or replacement fuse
or replacement of
electronics board
/
Manual
Compressor 1 sensor
defect
Compressor 1 sensor data is illogical
Both compressors stop
and also the fan
Automatic
after repair
Compressor 1
temperature defect
Compressor 1 overheating
(compressor temperature>115°C)
more than 24 times in 24 hours
Both compressors stop
Manual
Compressor 2
sensor defect
Compressor 2 sensor data is illogical
Both compressors stop
and also the fan
Automatic
after repair
Compressor 2
temperature defect
Compressor 1 overheating
(compressor temperature>115°C)
more than 24 times in 24 hours
Both compressors stop
Manual
flow
ERR
Zero flow
rate defect
"Zero flow rate" repeated
after 8 attempts
HP stopped
Manual
low flow
Insufficient flow
rate error
Difference in temperature too large between
heat pump inlet and outlet
Normal operation
Manual
Flow rate
detector defect
Flow rate inlet = 1
and
Heat pump CP outlet = 0
No HP start-up
= heat pump off and back-up on
(if authorised)
Automatic as soon as
flow rate =
0 and HPCP = 0
Zero flow
rate error
Flow rate inlet = 0
HP circulator pump = 1
No HP start-up
Automatic with Hp
circulator pump attempts
= 1 every 2 minutes
freq. defro
ERR
De-icing
too often
De-ices more than three times
per hour
HP stopped
,
only electrical back-up runs
(if authorised)
Manual
When an error occurs the backlighting flashes.
Any defect which stops the appliance from operating is indicated by an alarm .
When the error needs to be manually rectified the symbol is displayed.
compres
-
1
err
compres
-
2
err
flow detec.
err