Export Sys CFG
: The system sends a copy of the system configuration to the
USB memory. Selecting the number will save the parameters in the \DATAxx
folder. If there is a previous configuration, it overwrites the previous data.
•
Import Sys CFG
: It imports the data from folder DATAxx from the USB memory.
3.3.10 System configuration <System>
System general parameters configuration:
•
Run AutoSetup
: Launches the automatic system configuration by EN54. See
details at section 3.2 Automatic Configuration. <Run Autosetup>
•
Restart Device
. Restarts the system and internal processors.
•
Factory Reset
: Returns the system to its Factory configuration. It deletes all the
parameters configured by the user, except for the logs.
•
FW_Update
: Allows to actualize firmware version by a file in USB memory.
◦
NOTE: File must be in the root directory and be called
fw.bin
or
update.bin
•
Location:
User can edit the Label of this unit, this label will be visible in main
Screen.
•
Date/Time:
Edit system date and time.
3.4
Login. Access configuration
Login submenu allows to introduce the password to use the system. Otherways, the
user will be asked to introduce it automatically.
In the
Access Config
section passwords for each level could be personalized. A
password for PA (L1) management can be added and passwords for access levels L2
and L3 can be modified or deleted.
3.5
Advanced configuration
3.5.1 Equalizer setup
This menu is the same for each input and ouput configuration. It is detailed here as
advanced configuration.
•
Eq Enable:
Enable or Disable (bypass) the equalizer module.
•
Eq Settings:
◦
Band x/y:
Selection of band (X) to edit. (Y) is the available bands.
▪
Freq:
Frequency. 10Hz Steps (<1KHz) and 100Hz(>1KHz)
▪
Gain:
Steps of 1dB from -10 dB to +10 dB
▪
Width:
Filter width selection between 5 presets.
•
Wide 2(Q=0,5); Wide 1(Q=1); Mid(Q= 1,41); Narrow 1(Q= 2); Narrow 2
(Q= 4)
3.5.2 System Variables
Some configuration parameters are not available in the menu because they are not
common and they need a detailed information. This information will be available on LDA
support web.