CIE AutoReset:
With this active parameter the system leaves emergency when
releasing the input dry contact that activated it.
•
Status OUT N/C:
Configures the status output polarity for EMG and FLT
contacts.
•
RS485 Conf
. It configures the communication port parameters
◦
Baud Rate, Parity …
3.3.8 Battery charger. <Battery>
In the battery menu you can deactivate the battery monitoring, the integrated charger
and monitor the battery status.
•
Monitor
: In this section we can see battery state: voltage, impedance, charger
state, charge current and temperature.
•
Charger Enable
: It enables or disables the battery charger. If license is installed.
•
Supervision
: It enables battery state supervision and failure detection. Voltage is
checked each 60 seconds and internal impedance is measured every 10 minutes.
•
Temp Sensor
: It enables battery temperature sensor supervision. Is checked
every 60 s.
•
Faults Levels
: The minimum voltage of the battery and the maximum impedance
can be adjusted. Default values: 10,5 V and 200 mOhms. We recommend to
adjust impedance according to the battery used. For example for YUASA NP17-
12I model we recommend 50mOhm.
a) Battery charger Monitoring.
In order to help the user in the diagnostic of the battery state, the system has the
“Monitor” menu.
•
Voltage
: It indicates the actual voltage of the battery.
•
Impedance
: Battery impedance measured.
•
Chg status
: Charger status. It indicates the actual state of the charge:
◦
Disabled
: Disabled charger.
◦
Bulk
: Phase of maximum intensity of load when it is possible to reach 80% of
the load in the shortest time. It has a limit of 24h, if the system fails to complete
this stage it will indicate a fault “Chg timeout”.
◦
Absorption
: In this phase the charging current decreases progressively until
the battery reaches 100% charge. It also has a limit of 24 hours according to
regulation.
◦
Float
: Battery is totally charged and this is the state to keep it 100% charged.
This voltage will be between 13 and 13.8V normally.
•
Current
: It indicates the current charged in this moment.
•
Temperatura
: Temperature value of the battery sensor in Celsius degrees.
3.3.9 Save and charge configuration. <Load/Save>
The configuration system can be saved or charged.
17