INSTALLATION
MVE User Manual (710-17074-00G) |
25
6.13
CT Current Measurement
The MVE supports the summation and zero sequence methods of ground current measurement.
The line current transformers supplied with the soft starter are 1000:1 ratio. The MVE also supports customer-supplied 500:1 CTs
if required. If 500:1 CTs are used, the setting of switch S1 on the power interface board must be changed.
Summation method ground current measurement
•
Connection diagram: ground current summation CTs
L1
L2
L3
L21
L22
L
1
1
L12
L32
L31
GF
2
GF
1
2
3
1
17971.
C
1 Line current transformers (1000:1)
2 Ground current input to Power Interface PCB
3 Individual phase inputs to Power Interface PCB
•
Switch settings for summation method
NOTE
The soft starter will check the switch settings when control power is applied. If the switch settings are changed, control
power must be cycled for the new setting to take effect.
Line CT ratio
Switch setting
500:1
0100
1000:1
1100
•
Example settings for S1
1 1
0 0
= 1100
16533.
B
NOTE
Dip switch 1 on S1 is closest to the control terminal connectors. Dip switch 4 is closest to the CT connectors.