PROGRAMMABLE PARAMETERS
2F –
Stop Mode
Options:
Coast To Stop
TVR Soft Stop (default)
Adaptive Control
Description:
Selects the stop mode.
2G –
Stop Time
Range:
0:00 - 4:00 (minutes:seconds)
Default:
0 second
Description:
Sets the time for soft stopping the motor using timed voltage
ramp or Adaptive Control.
If a main contactor is installed, the contactor must remain
closed until the end of the stop time. Use the main contactor
output (33, 34) to control the main contactor.
2H –
Adaptive Stop Profile
Options:
Constant Deceleration (default)
Description:
Selects which profile the EMX4e will use for an Adaptive Control
soft stop.
2I –
Adaptive Control Gain
Range:
1% - 200%
Default:
75%
Description:
Adjusts the performance of Adaptive Control. This setting
affects both starting and stopping control.
2J –
Multi Pump
Options:
Single Pump (default)
Manifold Pump
Description:
Adjusts the performance of adaptive control to suit installations
with multiple pumps connected to a common outlet manifold.
2K –
Start Delay
Range:
0:00 - 60:00 (minutes:seconds) Default:
0 second
Description:
Sets a delay after the starter receives a start command, before it
starts the motor.
9.7
5 Protection Levels
5A –
Current Imbalance
Range:
10% - 50%
Default:
30%
Description:
Sets the trip point for current imbalance protection.
60 |
EMX4e User Manual (710-18433-00C)