SYSTEM DESIGN
Environmental
Operating temperature .................... -10 ˚C~60 ˚C, above 40 ˚C with derating
Storage temperature .................................................................. -25 °C~+ 60 °C
Operating Altitude ............................... 0~1000 m, above 1000 m with derating
Humidity ................................................................... 5%~95% Relative Humidity
Pollution degree .................................................................... Pollution Degree 3
Vibration ........................................................................................ IEC 60068-2-6
Protection
EMX4e-0024B~EMX4e-0135B ................................................................ IP20
EMX4e-0184B~EMX4e-0580B ................................................................ IP00
Heat dissipation
During Start ...................................................................... 4.5 watts per ampere
During Run
EMX4e-0024B~EMX4e-0052B .......................................... ≤ 35 watts approx
EMX4e-0064B~EMX4e-0135B .......................................... ≤ 50 watts approx
EMX4e-0184B~EMX4e-0250B ........................................ ≤ 120 watts approx
EMX4e-0352B~EMX4e-0580B ........................................ ≤ 140 watts approx
Motor Overload Protection
Default: The default settings of parameters 1C, 1D and 1E provide Motor Overload
Protection: Class 10, Trip Current 105% of FLA (full load amperage) or equivalent.
Certification
CCC ..................................................................................................... GB 14048.6
CE ...................................................................................................... EN 60947-4-2
C-UL ...................................................................................... C22.2 Nº 60947-4-2
UL .................................................................................................... UL 60947-4-2
RCM ............................................................................................... IEC 60947-4-2
Operational life (internal bypass contacts)
............................................................................................ 100 000 operations
3.15
Disposal Instructions
Equipment containing electrical components may not be disposed
of together with domestic waste.
It must be collected separately as electrical and electronic waste
according to local and currently valid legislation.
EMX4e User Manual (710-18433-00C) |
21