SYSTEM DESIGN
3.11
IEC Coordination with Short Circuit Protection Devices
These fuses were selected based on start current of 300% FLC for 10 seconds.
Nominal Rating
(A)
SCR I
2
t (A
2
s)
Type 1
coordination
480 VAC, 65 kA
Bussmann
NH fuse links
Type 2
coordination
600 VAC, 65 kA
Bussmann
DIN 43 653
EMX4e-0024B
24
1150
40NHG000B
170M3010
EMX4e-0042B
42
7200
63NHG000B
170M3013
EMX4e-0052B
52
80NHG000B
EMX4e-0064B
64
15000
100NHG000B
170M3014
EMX4e-0069B
69
EMX4e-0105B
105
80000
170M3015
EMX4e-0115B
115
160NHG00B
EMX4e-0135B
135
125000
170M3016
EMX4e-0184B
184
320000
250NHG2B
EMX4e-0200B
200
170M3020
EMX4e-0229B
229
315NHG2B
EMX4e-0250B
250
170M3021
EMX4e-0352B
352
202000
355NHG2B
170M6009
EMX4e-0397B
397
400NHG2B
EMX4e-0410B
410
320000
425NHG2B
170M6010
EMX4e-0550B
550
781000
630NHG3B
170M6012
EMX4e-0580B
580
EMX4e User Manual (710-18433-00C) |