SYSTEM DESIGN
3.4
Current Ratings
Contact your local supplier for ratings under operating conditions not covered by
these ratings charts.
IEC ratings
•
AC53b format (bypassed current rating)
80 A : AC-53b
3.5 - 15 : 345
Off time (seconds)
Start time (seconds)
Start current (multiple of motor full load
current)
Starter current rating (amperes)
•
Ratings
All ratings are calculated at altitude of 1000 metres and ambient temperature of
40 ºC.
3.0-10:350 3.5-15:345 4.0-10:350 4.0-20:340 5.0-5:355
EMX4e-0024B
24
20
19
16
17
EMX4e-0042B
42
34
34
27
32
EMX4e-0052B
52
42
39
35
34
3.0-10:590 3.5-15:585 4.0-10:590 4.0-20:580 5.0-5:595
EMX4e-0064B
64
63
60
51
54
EMX4e-0069B
69
69
69
62
65
EMX4e-0105B
105
86
84
69
77
EMX4e-0115B
115
108
105
86
95
EMX4e-0135B
135
129
126
103
115
EMX4e-0184B
184
144
139
116
127
EMX4e-0200B
200
171
165
138
150
EMX4e-0229B
229
194
187
157
170
EMX4e-0250B
250
244
230
200
202
EMX4e-0352B
352
287
277
234
258
EMX4e-0397B
397
323
311
263
289
EMX4e-0410B
410
410
410
380
400
EMX4e-0550B
550
527
506
427
464
EMX4e-0580B
580
579
555
470
508
EMX4e User Manual (710-18433-00C) |
9