APPLICATION EXAMPLES
11.3
Emergency Run Operation
In normal operation the EMX3 is controlled via a remote two-wire signal (terminals C31, C32).
Emergency Run is controlled by a two-wire circuit connected to Input A (terminals C53, C54). Closing Input A causes the EMX3 to run
the motor and ignore certain trip conditions.
NOTE
Although the Emergency Run satisfies the functionality requirements of Fire Mode, AuCom does not recommend its use
in situations that require testing and/or compliance with specific standards as it is not certified.
CAUTION
Continued use of Emergency Run is not recommended. Emergency Run may compromise the starter life as all
protections and trips are disabled.
Using the starter in 'Emergency Run' mode will void the product warranty.
32
31
6/T3
2/T1
13
14
P24
COM
4/T2
24
23
34
B10
B11
41
42
44
B5
B4
C31
C32
C41
C42
C53
C54
C24
C64
C63
B7
B8
B6
A2
A1
A3
5/L3
3/L2
C23
E
1/L1
7
6
5
4
3
2
1
8
9
05971.
D
1
Control voltage (model dependent)
2
Remote control inputs
3
Motor thermistor input
4
RTD/PT100 input
5
24 VDC output
6
Relay outputs
7
Analog output
8
Three-phase supply
9
Motor terminals
S1
Start/stop contact
S2
Reset contact
S3
Emergency Run Contact
F1
Semiconductor fuses (optional)
13, 14
Relay output A
23, 24
Run relay output
31, 32, 34
Relay output B
41, 42, 44
Relay output C
Parameter settings:
•
Parameter 6A
Input A Function
•
Select 'Emergency Run' - assigns Input A for Emergency Run function.
•
Parameter 15C
Emergency Run
•
Select 'Enable' - Enables Emergency Run mode.
64