AUBER INSTRUMENTS
WWW.AUBERINS.COM
2013.05
P1/3
Instruction Manual
SYL-1615 Temperature Controller for Charcoal Smoker
Version 1.1
2. Specifications
AC adaptor: 100-240V, 50/60Hz input. 12 VDC, 1 Amp output.
Power consumption: <2W
Sampling rate: 4 samples/second
Accuracy: 0.2% full scale
Display range: -320~2400°F, or -200~1300°C
SSR output for Fan: 12VDC, 1 Amp*
LED display: 0.39 inch, red
Control Mode: PID, On/off, Limit.
Alarm: Two set points with buzzer sound.
Sensor: K type thermocouple, -300~550°F (-200~300°C).**
Dimension: 2.8x3.5x1.2" (70x90x30mm)
* Up to 3 Amp can be supplied when more powerful power supply is used.
** Eight other types of thermocouple can also be accepted (see table 4)
3. Front Panel
1. Features
This PID controller is for controlling the temperature of charcoal smoker. It will regulate
the on/off time interval of a 12VDC blower to stabilize the temperature in the charcoal
smoker. It has built-in solid state relay that can drive a 12V DC operated blower up to
60 CFM. It has a built-in buzzer that can be set for both low limit and high limit alarm.
The system includes a controller, an AC to 12V DC adaptor, a K type thermocouple.
Also included is power plug that fits the control output jack. User needs to install the
plug to a 12V DC operated blower with adequate wind speed (5 CFM Fan is the most
common for a small smoker).
5. Parameter Setting
①
POWER-12V Power supply input
②
OUT- Fan control output
③
INPUT-Temperature probe input
Figure 2 shows the terminals of the controller. Connect the AC to 12V DC power
adapter to the terminal 1 and wall outlet. Connect the fan connector to terminal 2. The
polarity for this socket is center pin positive (+), outer collar negative (
−
). Connect the
K thermocouple to terminal 3. Please note that thermocouple connector also has
polarity. The wide blade should go to the wide slot.
4. Connecting the Controller
Note 1. Set Temperature.
There are two ways to set the target temperature.
a. During the normal operation mode, press
Λ
or V once to switch the display from
process value (PV) to set value (SV, or target temperature). The display will start to
blink. Press
Λ
or V again to increase or decrease the SV. When finished, wait 8
seconds and the settings will take effect automatically (the display will stop blinking).
b. Press SET key once. Use >,
Λ
and V keys to enter code 0001. Press SET key to
confirm, then the display would be SV (
Su
). Press SET key again to display the SV
setting. Use >,
Λ
and V keys to enter the new SV value and press SET to confirm.
Press V key to change the display to END. Then, press SET to exit. You can also
ignore the steps after confirmation of SV. The controller will return to normal operation
mode automatically if no key is pressed for 1 minute. The flow chart below shows how
to set the SV and alarms in details.
Symbol
Range
Note
SV
Target temperature
AH1
Alarm 1 on temperature
End
Exit
AL1
Alarm 1 off temperature
AH2 Alarm 2 on temperature
AL2 Alarm 2 off temperature
Description
Initial
SV
AH1
End
AL1
AH2
AL2
200
250
249
250
250
Note 1
Arbitrary value
within the
measuring range
Figure 3. Flow chart for how to set target temperature and alarm.
5.1. Temperature setting and Alarm setting (accessed by code 0001)
Table 1. Temperature and alarm parameters
Figure 2. Terminals (back view)
Note 2
Operation Mode
XXXX
0001
Enter Code
Parameter Display
Buzzer On Temp
sv
0200
0250
0250
Target Temp Selection
0249
ah1
al1
ah2
end
Buzzer Off Temp
Buzzer On Temp
SET
SET
SET
SET
SET
SET
SET
SET
0250
al2
SET
SET
SET
SET
SET
Buzzer Off Temp
Figure 1. Front panel
①
②
③
④
⑤
⑥
⑦
①
②
③
①
Parameter display
②
OUT-SSR output indicator
(AT)-Blinking during auto-tune process
③
Set/Confirm
④
Digit shift/Alarm mute/Auto-tune
⑤
Value decrement/Select previous parameter
⑥
Value increment/Select next parameter
⑦
AL-Alarm Indicator
Summary of Contents for SYL-1615
Page 4: ......