SYL-53X2P(A) USB PID Controller Quick Guide 

Version 1.5 (Oct, 2020) 

 

 

Caution

  

 

This  controller  is  intended  to  control  equipment  under  normal  operating 
conditions.  Failure  or  malfunction  of  the  controller  may  lead  to  abnormal 
operating  conditions,  which  result  in  personal  injury  or  damage  to  the 
equipment  or  other  property.  Devices  (limit  or  safety  controls)  or  systems 
(alarm  or  supervisory)  intended  to  warn  of  or  protect  against  failure  or 
malfunction of the controller must be incorporated into and maintained as part 
of the control system. 

 

This  controller  carries  a  90-day  warranty.  This  warranty  is  limited  to  the 
controller only. 
 

1.

 

Terminal wiring 

1
2
3

13 14 6

7
8
9

10

4
5

AL2

AC

85~240V

SSR

+

-

R

R

W

TC

-

+

11 12

RTD

RS485

A+

B-

AL1

SYL-

5352PA

 

1
2
3

13 14 6

7
8
9

10

4
5

AL2

AC

85~240V

R

R

W

TC

-

+

11 12

RTD

RS485

A+

B-

AL1

SYL-

5342P

Out

 

Figure 1. Wiring terminals of SYL-5352PA & SYL-5342PA. 

 

2.

 

USB adapter wiring (IMPORTANT!) 

 

Locate the pin A and B on the back of the USB adapter. 

 
 

 

 

 

 
Use the included 2-lead cable to 

connect terminal 11 (A) on the PID to A mark 

on USB adapter

, and 

connect terminal 12 (B) on the PID to B mark on USB 

adapter

. Recommend to use yellow wire to connect between two A pins, and 

use silver wire to connect between two B pins.  
 

Please note, USB cable on terminal 11 & 12 must be secured and isolated 
from the power input cable on terminal 9 & 10. Otherwise high voltage AC 
power from the power input cable may damage your USB adapter and/or 
your computer. 

 

3.

 

Operation tips: 

Program Start/Resume:

 Press and hold UP key for 2s, A-M indicator will be 

solid ON. 

Program HOLD:

 Press and hold UP key for 2s, display will flash HOLD and A-

M indicator will be flashing. 

Program STOP:

 Press and hold SET and A/M key together for 3s, you will see 

SEC on the top. Press SET key 4 times momentarily, and you will see RUN on 
the top. Use UP and DOWN keys to change its value to 1. Press SET key again 
to confirm. Leave the PID for couple seconds and it will exit automatically.  

Program STOP and go back to step 1 (SYL-5342PA & SYL-5352PA or newer 
models):

  Press  and  hold  DOWN  arrow  key  for  about  3s,  the  lower  display 

window will show “

stop

. The program is stopped and jumped back to step 1. 

Program  STOP  and  go  back  to  step  1: 

Press  and  hold  SET  and  A/M  key 

together for 3s, to enter menu, then change both RUN and Pro back to 1.  

 

4.

 

Recommended settings: 

This controller has two layers of menus. One menu is for parameters, another 
menu for step programming and step control parameters.  
 
Press and hold SET key for 3s to enter parameter setting menu. Then press SET 
key momentarily to confirm and go to next parameter. See all its parameters in 
its complete manual below. Here are recommended changes on the setting: 
 

P = 100:

 By default, P=0 for ON/OFF mode (like thermostat). For PID mode, 

please change P parameter to 100 (recommended value). If you don’t have good 

control result, please run auto-tune.  

T = 2 or 20:

 T is output cycle time. For SSR output controller (SYL-5352PA), 

please change T to 2s. For relay output (SYL-5342PA), please change T to 20s.  

dP = 0: 

dP is for display decimal point. 

If you don’t need 0.1 degree accuracy, 

change dP to 0 and it will show integral number only.  

CF = F: 

Change temperature display unit to Fahrenheit. Default is Celsius.

 

PuH = 2500:

 PuH decides the maximum display temp. Default is 1300 degree, 

may not good for high temp application like kiln.  
 
Press and hold SET key and A/M key together for 3s to enter step programming 
setting. Here are recommended changes on the setting: 
 