RDK-300B Controller for Hot Runner Coil Heater 

Version 1.0 (April, 2020) 

 
 

 

Caution

 

 

Check pin assignment before connecting a coil to the controller (see section 
3.4). The pin assignment on RDK-300 is different from RDK-100.  

 

The default set temperature on RDK-300B is 300°F. The controller will start 
to heat the coil immediately after it is power up if coil is connected. Please 
make sure the coil is placed in a secure place before power up.  

 

The coil heater should NOT be heated above 1000°F. By default, the auto-
shutoff temperature and time are set to 900°F and 60 minutes. 

 

When controller is turned off, the coil will stay at very high temperature for at 
least 20 minutes. DO NOT TOUCH the coil until controller stops flashing 
“Hot”. The heated coil is very dangerous. It will cause severe burn if touched.  

 

One (1) year warranty for the controller; six (6) months for the coil heater* 
 

Note: * Our warranty for coil heater only covers manufacturing defects; it does NOT cover 
damages caused by high temperature (≥ 1000°F) use.    

 

1.

 

Specification 

Controller 

Operating voltage

 

120 V / 240 V AC

 

Maximum current

 

5 Amp

 

Input power connection

 

IEC 320 C14

 

Coil connection

 

XLR 5 Pin

 

Dimension

 

3.5 x 1.7 x 4.7 inch, (90 x 47 x 120 mm)

 

Temperature control range

 

200°F to 1000 °F

 

 
 

2.

 

Front Panel             

 

② 

 

Figure 1. Front Panel. 

 

① 

Current temperature 

② 

Output status indicator 

 

 

③ 

Set temperature

 

 

④ 

Power button with stand-by status indicator

 

 

⑤ 

Control knob. Access menu and change parameters

 

 

3.

 

Getting Started 

 

3.1

 

Confirm the Pin Assignment on the Heater Coil  

Before you plugging any coil to this controller, please confirm that the coil has 
the same pin assignment (see Table 1) as the RDK-300B.  
 

Table 1. Pin Assignment of the XLR connector on RDK-300B. 

AC Power to Heater

 

AC Power to Heater

 

TC +

 

TC -

 

Ground

 

 
 

3.2

 

Connecting the Coil Heater 

To  connect  the  coil  heater,  align  the  slot  on  the  XLR  connector  on  the  coil 
cable  with  the  tab  on  the  female  XLR  connector  on  the  controller,  and  then 
push it in. To disconnect it, press the “PUSH” tab on the female connector and 
pull the connector out. 

 

Warning

With a coil connected, 

the controller will start to heat 

the coil immediately

 after it is power up. Please make sure that the 

coil is placed in a secure place before power up. When controller is 
turned off, the coil will stay at a very high temperature for at least 20 
min. Controller will flash “hot” and coil temperature at top display, 
and it will show “off” at bottom display. DO NOT TOUCH the coil until 
the controller stop flashing “hot”. The heated coil is very dangerous. 
It will cause severe burn if touched. 

 It is strongly recommended 

that the power cord should be unplugged after use.

  

 
 
3.3

 

Power On/Off the Controller 

Connecting  the  power  cord  to  the  controller  and  to  the  wall  outlet,  then  the 
power button should light up in red, which means the controller is in standby 
status. The displays should still be dark and there should be no power output to 
the coil heater. Press down the power button briefly, the display should turn on 
and  the  power  button  will  lit  in  white.  The  bottom  of  the  display  window  will 
show  the  set  temperature  value,  and  the  top  display  window  will  show  the 
current  coil  temperature.  Controller  will  start  heating  up  the  coil  to  the  set 
temperature. If no coil is plugged in, the top display will show “

-H-

“.  

 
To power off the controller, press down the power button briefly. Controller will 
cut  off  power to  the  coil,  keep  displaying  the  coil  temperature  till it  is  cooled 
below a safe cool temperature.   
 
 

3.4

 

Basic Operations 

This controller has two operating mode, 

standard mode

 and 

boost mode

 

(which is newly added to RKD-300B). By default, the controller will first power 
up in standard mode.  
 

Instruction Manual

 