Video Loss Action Setup
The Video Loss Action Setup screen allows the user to set up the action the multiplexer
takes when there is a video loss condition.
Buzzer: When set to ON, the multiplexer’s internal buzzer sounds upon a video loss
condition.
Alarm Screen: When set to ON, the screen display changes to the one defined in the
Alarm Screen Format menu during a video loss condition.
Internal Relay: Selects which internal relays will be activated during a video loss
condition. Option 1 selects relay 1. Option 2 selects relay 2. Option 1&2 activates both
internal relays. Select OFF to de-activate both internal relays.
Network Relay: When set to ON, the multiplexer sends the video loss information to an
external relay box via the network during a video loss condition.
Message Latch: When set to ON, a “V” displays on the screen when a video loss
condition occurs. It remains on the screen until it is cleared.
Spot Monitor 1 – 4: When set to ON, the Spot Monitor displays the camera with a video
loss condition. When there are multiple alarms, cameras with alarms will display
sequentially. When set to OFF, the Spot Monitor’s display does not change during a
video loss condition. (1 AUX on 4-ch unit; 4 AUX on 9-ch and 16-ch units)
Hold Time: The Hold Time setting allows the user to set the alarm actions to last from 1
to 99 seconds.
Manual Alarm Action Setup
There are two screens for the Manual Alarm Action Setup as shown below. The Next and
Back buttons toggle between the two screens. The Exit button saves the settings and
returns to the main Alarm Setup menu.