SuperTrak™ GEN3 System Operation and Maintenance Manual
Rev. 9 (12-2021)
Technician Procedures
Replace an Electrical Interconnect
Replace a Section-to-Section Electrical Interconnect--Rigid Connection
Remove the existing rigid conduit
1. Turn the
SuperTrak conveyance platform power disconnect switch
to
the OFF position.
2. Lock out and tag hazardous energy.
3. Open the electrical doors of the two (2) adjacent sections.
4. Disconnect and remove all wires that run through the metal conduit.
5. Loosen the strain relief connectors on the side of the two (2) adjacent sections.
6. Slide the metal conduit out through the
cable access hole.
Slide the metal conduit to the right, so it
exits through the left side of the electrical
panel.
Install the replacement rigid conduit
1. If required, remove the existing electrical interconnect, as described above.
2. Slide the metal conduit in through the
cable access hole and the two (2) strain
relief connectors.
Always start the metal conduit from left
side of the section’s electrical panel.
For a wiring overview, see the wiring pin-out overview label located on
the electrical door of each straight section and curved section during this
procedure.
Summary of Contents for SuperTrak GEN3
Page 1: ...Rev 9 December 2021...
Page 2: ......
Page 3: ...SuperTrak GEN3 Conveyance Platform Modular Conveyor Operation and Maintenance Manual...
Page 6: ......
Page 12: ...This page is intentionally blank...
Page 30: ...This page is intentionally blank...
Page 58: ...This page is intentionally blank...
Page 296: ...This page is intentionally blank...
Page 300: ...This page is intentionally blank...
Page 364: ...This page is intentionally blank...
Page 366: ...This page is intentionally blank...