
Operating Procedures
SuperTrak™ GEN3 System Operation and Maintenance Manual
135
Rev. 9 (12-2021)
Measure the Resistance Between the Common
Connection and the 24V Digital Power Connection
1. Test the resistance as shown below:
2. Look at the value displayed on the multimeter screen and determine if the
resistance is acceptable:
•
Pass - The value is initially <500
Ω
and then quickly rise to >1000
Ω
.
This occurs because the capacitors are charging.
•
Fail - The value quickly settles at <5
Ω
. This indicates that a short
exists.
A short exists between the 24V digital power connection and the
Summary of Contents for SuperTrak GEN3
Page 1: ...Rev 9 December 2021...
Page 2: ......
Page 3: ...SuperTrak GEN3 Conveyance Platform Modular Conveyor Operation and Maintenance Manual...
Page 6: ......
Page 12: ...This page is intentionally blank...
Page 30: ...This page is intentionally blank...
Page 58: ...This page is intentionally blank...
Page 296: ...This page is intentionally blank...
Page 300: ...This page is intentionally blank...
Page 364: ...This page is intentionally blank...
Page 366: ...This page is intentionally blank...