Figure 2.120 Webpage to Configure Modbus Setting
Table 2.108 Descriptions of Modbus Setting PortConfiguration
Label
Description
Factory
Default
Modbus Address
Identifier for modbus slave device, range from 1 to 247
1
Click
Save
button to save the setting configuration. Click
Reset
button to undo any changes made locally and revert to
previously saved values.
Users can use Modbus TCP/IP compatible applications such as
Modbus Poll
to configure the switch. Note that Modbus Poll
can be download
from
. The Modbus Poll 64-bit version 9.2.2, Build 1343 was
used in this document. Atop does not provide this software to the users. Tutorial of Modbus read and write examples are
illustrated below.
Note
:
The switch only supports Modbus function code 03, 04
(
for Read
)
and 06
(
for Write
).
Read Registers (This example shows how to read the switch’s IP address.)
Figure 2.119 Mapping Table of Modbus Address for Switch’s IP Address
1.
Make sure that a supervising computer (Modbus Master) is connected to your target switch (Modbus Slave) over
Ethernet network.
2.
Launch
Modbus Poll
in the supervising computer. Note a registration key may be required for a long-term use of
Modbus Poll after 30-day evaluation period. Additionally, there is a 10-minute trial limitation for the connection to
the managed switch.