43
44
PV Input data
DC voltage range(V)
MPP operating voltage range(V)
Max. power(W)
Number of MPPT
Inputs per MPPT
Nominal Output Current(A)
Max. Output Current(A)
AC Grid output data
Rated voltage(V)
Operating voltage range(V)
Operating frequency(Hz)
Operating frequency range(Hz)
Phase shift
Reactive power adjust range
THDI
UPS AC output data
Nominal output current(A)
Rated output power(VA)
Operating frequency(Hz)
THDV
Switching Time
Efficiency
Max. Efficiency @ PV to grid
Max. Efficiency @ battery to grid
Battery data
Type
Max. charge current(A)
Max. discharge current(A)
Nominal voltage(V)
Voltage range(V)
Integrated disconnect
Reverse polarity protection
DC switch rating for each MPPT
Output over-voltage protection varistor
General Data
Output over current protection
Ground fault monitoring
Grid monitoring
Pole sensitive leakage current Monitoring unit
RSD
Dimensions(mm)
Weight(kg)
12K
50
50
@240V 12000/@208V 10400
Sync inrush curent(A)
Nominal power output(W)
Nominal output voltage(V)
Degree of protection
Max. usable input current(A)
Max. short circuit input current(A)
Start input voltage(V)
Startup voltage(V)
Full power MPPT voltage range(V)
DC nominal voltage(V) MPPT tracker
230-500
AFCI
Peak power(VA)
MPPT Efficiency
Cooling concept
Relative humidity
Altitude(m)
Noise emission(dB)
Internal consumption(W)
Topology
Display
Communication interface
Standard warranty
50
@240V 12000/@208V 10400
18000
250
250
25/15/15
34/17/17
100
140
100-600
120-500
360
3
2/1/1
180-270
240
-0.8~+0.8 leading Adjustable
60
55-65
<3%
35
0.99@full load
[240][120/240][120/208]
<3%
<20
60
97.5%
94%
99.9%
48
40-60
Lead-acid battery/Lithium battery
Yes
DC switch
Yes
Yes
Yes
Yes
Yes
Yes
YES
670*490*265mm(22.8*19.3*10.4inch)
50kg(96.8 Ibs)
NEMA4X / IP 65
FAN
YES
0-100%
<2000m
<50dB
<15W
Touch color screen
Transformer-less
5years
Rs485/ Wi-Fi/ CAN
2xPn, 0.5s
When the grid voltage exceeds V1, the output active power varies with the grid voltage.
Note: When setting the protection time, it needs to be converted into the number of cycles of the
corresponding frequency;
6.2.10 Active power limit mode
V2
1.1*Un
Parameter name
Default Value
106%Vnom
V1
P1
Ppre-disturbance (for
active power output at
the time voltage exceeds
V1 in p.u. of Prated)
Pmin (for Advanced
Inverters that can only
inject active power,
Pmin should approach 0)
10S
Open Loop
Response Time
P2
Disable
Voltage-Active
Power Mode
1.04*Vn
Minimum
Adjustable Range
105%Vnom
0.5S
N/A
1.10*Vn
Maximum
Adjustable Range
109%Vnom
60S
N/A
N/A
N/A
N/A
N/A
Parameter name
Default Value
100
Maximum Active Power(%)
Enable
Active power limit mode
Minimum
Adjustable Range
0
N/A
Maximum
Adjustable Range
100
N/A
6.3 Test parameter tolerances
Parameter
Units
Current
Volts
±
1%Urated
Amps
±
1%Urated
Watts
±
1%Urated
Power
Default Tolerance
of Measurement
Reactive Power
Power Factor
Voltage
VA
Displacement
power factor
Hz
Frequency
Response Time
Time accuracy
Seconds
Total time
±
5%Srated
±
0.01
±
0.05
1
0.1%
Operating temperature range (
℃
)
-25~60
℃,>
45
℃
Derating