6.2.2   High Voltage and Low Voltage Trip

Grid Volt Limit1 Low Time

Grid Volt Limit1 Low(V)

88%Vnom

Required settings 
in accordance 
with UL 1741 SA

Parameter name

Default 

Value

High voltage 2 HV2

High voltage 1 HV1

110%Vnom

Grid Volt Limit1 High(V)

Grid Volt Limit1 High Time

13s

21s

Low voltage 1 LV1

Low voltage 2 LV2

Note: When setting the protection time, it needs to be converted into the number of cycles of the 

corresponding frequency;

50%Vnom

Grid Volt Limit2 Low(V)

Grid Volt Limit2 Low Time

2s

120%Vnom

Grid Volt Limit2 High(V)

Grid Volt Limit2 High Time

160ms

0%Vnom

Minimum 

Adjustable Range

110%Vnom

1s

2s

0%Vnom

160ms

Fixed at 120%Vnom

Fixed at 160ms

88%Vnom

Maximum 

Adjustable Range

120%Vnom

13s

50s

50%Vnom

21s

Fixed at 120%Vnom

Fixed at 160ms

6.2.3   High Frequency and Low Frequency Trip

Grid Freq Limit1 Low Time

Grid Freq Limit1 Low(V)

58.5Hz

Required settings 
in accordance 
with UL 1741 SA

Parameter name

Default 

Value

High Frequency 2 HF2

High Frequency 1 HF1

61.2Hz

Grid Freq Limit1 High(V)

Grid Freq Limit1 High Time

300s

300s

Low Frequency 1 LF1

Low Frequency 2 LF2

Note: When setting the protection time, it needs to be converted into the number of cycles of the c

orresponding frequency;

56.5Hz

Grid Freq Limit2 Low(V)

Grid Freq Limit2 Low Time

160ms

62.0Hz

Grid Freq Limit2 High(V)

Grid Freq Limit2 High Time

160ms

50.0Hz

Minimum 

Adjustable Range

61.0Hz

180s

180

50.0Hz

160ms

61.8Hz

160ms

Maximum 

Adjustable Range

59.0Hz

66.0Hz

1000s

1000s

57.0Hz

1000s

66.0Hz

1000s

6.2.4  Specified Power factor (SPF)

Parameter name

Default Value

1

Constant Power Factor

The reactive power is controlled as a function if a specified power factor cos

φ

Disable 

Constant Power Factor Mode

Under-excited/Over-excited

Under-excited

Minimum 

Adjustable Range

0.8

N/A

Under-excited

Maximum 

Adjustable Range

1

N/A

Over-excited

Note: Use the selected method to set Under-excited/Over-excited

39

40

6.2.5   Voltage / Var Mode ( Q(V))

The reactive power is controlled as a function of the grid voltage. The parameterize-action is carried out 

by means of a reactive power/voltage characteristic curve. The absolute value of Q1 and Q4 are the same.

Vref-3%Vnom

Parameter name

Default Value

Minimum 

Adjustable Range

Voltage-Reactive 

Power Mode

Disable 

N/A

100%Vnom

300s

Disable

95%Vnom

300s

0

-60% of nameplate 

apparent power

100%Vnom

105%Vnom

N/A

Vref-2%Vnom

0

Vref+2%Vnom

5000s

60% of nameplate 

apparent power

100%Vnom

60% of nameplate 

apparent power

Vref+3%Vnom

Maximum 

Adjustable Range

Vref

Vref adjustment 

time constant

Autonomous VRef 

adjustment Enable

V2

Q2

V3

Q3

N/A

N/A

Vref-18%Vnom

Open Loop 

Response Time

-60% of nameplate 

apparent power

Vref+18%Vnom

Vref-8%Vnom

44% of nameplate

apparent power

Vref+8%Vnom

44% of nameplate

apparent power

60% of nameplate 

apparent power

V2-2%Vnom

60% of nam eplate 

apparent power

V3+2%Vnom

V1

Q1

V4

Q4

-60% of nameplate 

apparent power

-60% of nameplate 

apparent power

5s

1s

90s

Summary of Contents for ATL12KW2897-22

Page 1: ...Version EN UM 1 0 00 Atlas Energy Solutions 848 W 1440 N suite 120 Logan UT 84321 1 435 233 6115...

Page 2: ...CT Meter connection 3 6 4 13 Working with Generator 3 7 15 Generator system connection 3 7 1 15 Generator Startup and stop settings 3 7 2 17 Monitor System Setup 3 10 21 3 10 1 3 10 2 Wifi GPRS 4G WLA...

Page 3: ...can interconnected with the utility grid Avoid misoperation and Inappropriate Usage All the work of this product system design installation operation setting configuration and maintenance must be car...

Page 4: ...system B AC Coupling with existed solar system C On grid solar system without battery Support EPS even without battery D Off grid and back up applications E Single and three phase paralleling system...

Page 5: ...ing bracket then drill 4 holes of 8mm 5 16inch diameter and make sure the depth of the holes is deeper than 50mm 2inch Step3 Hang the inverter onto the wall mounting bracket and lock the inverter on t...

Page 6: ...CAN RS485 please check Chapter 3 5 2 for Pin definition please check Chapter 3 9 for Parallel connection e Parallel communication port f FAN1 2 3 g TEMP Connection for temperature sensor of lead acid...

Page 7: ...duit fittings are fastened reliably and seal the cable entry holes 3 5 Battery Connection 3 5 1 Battery power cable connection 2 3 0 4 0 AWG 85 100 mm 600V Cable Requirement 12K Step 2 Route the batte...

Page 8: ...y master and slave settings 1 The temperature sensor for lead acid battery is optional If you need it please contact distributor for purchasing For Li ion battery For Lead acid battery 2 There are thr...

Page 9: ...talled at the service entry point in or near the main service panel We standard supply 2 CT for one inverter The CT interface for 2 CTs connection is a RJ45 port we have made a RJ45 plug on those 2 CT...

Page 10: ...ter Service Disconnect Generator Inverter Disconnect Generator Disconnect Backup Panel Generator Connection Whole Home Backup PE N PE L1 L2 PE N L2 L1 PE N L2 L1 2 wire start CT 2 CT 1 When generator...

Page 11: ...kw h 10A Generator Start Conditions Generator Stop Conditions when battery voltage or SOC higher than Charge end Volt SOC settings value When grid is off the hybrid inverter will work as a power sourc...

Page 12: ...erent using scenarios Up to 10 units can be paralleled to reach a capacity of 120kW Wiring diagram is as below The manual bypass switch connect loads to EPS panel for default When inverters fail users...

Page 13: ...ur mobile phone to the BAxxxxxxxx wireless network where BAxxxxxxxx is the serial number of the WiFi dongle luxpower_5G luxpowertek luxpowertek_5g HF WIFI ChinaNet EWP ChinaNet wG49 CMCC BAKR luxpower...

Page 14: ...arallel cable communication Interface DRM Interface Meter INV485 4 Operation Guide 4 1 Operation Mode The inverter has different working mode to meet customers various demands the working modes are as...

Page 15: ...2 3 1 Import Power Example 4 1 3 AC Charge Mode Users can charge battery with grid power when electricity price is cheap and discharge battery power to supply load or export to the grid when electric...

Page 16: ...m of the screen you ll see all current and historical fault warning information on this page Alarm record M8 Rx fault Inconsistant Fault status Fault record Alarm status M3 Rx failure Model fault Rese...

Page 17: ...its CT ratio is either 1000 1 or 3000 1 and set it accordingly the battery brand in the Lithium brand drop down list Meter type Please select it according to the meter that s to be installed Offgrid...

Page 18: ...ntact Luxpower service or your inverter supplier 1 Check if the L1 L2 and N wires are connected correctly at inverter EPS output port 2 Disconnect the EPS breaker to see if fault remains If fault pers...

Page 19: ...n EPS port Restart inverter If fault still exists contact Luxpower service or your inverter supplier Check if meter communication cable is connected correctly on inverter and meter side RSD Active Off...

Page 20: ...llowing up the below diagram if there is problem with the fans Turn off the system and wait for more than 5 minutes before disassembling the machine c Loosen the screws and remove them d Remove the fa...

Page 21: ...an activation the Rule21 function Setting the value in the corresponding blank Before setting you can read the default value first and then set the parameter of the function that needs to be modified...

Page 22: ...mum Adjustable Range 61 0Hz 180s 180 50 0Hz 160ms 61 8Hz 160ms Maximum Adjustable Range 59 0Hz 66 0Hz 1000s 1000s 57 0Hz 1000s 66 0Hz 1000s 6 2 4 Specified Power factor SPF Parameter name Default Valu...

Page 23: ...Q2 Q3 Constant Reactive Power 44 of nameplate apparent power Parameter name Default Value Under excited Under excited Over excited Disable Constant Reactive Power Mode Minimum Adjustable Range Under e...

Page 24: ...208V 10400 18000 250 250 25 15 15 34 17 17 100 140 100 600 120 500 360 3 2 1 1 180 270 240 0 8 0 8 leading Adjustable 60 55 65 3 35 0 99 full load 240 120 240 120 208 3 20 60 97 5 94 99 9 48 40 60 Le...

Reviews: