Type
Cables (90° cable) CEC
C22.1
Fuses RK5
(A)
Fuses LPJ
(A)
Maximum cable
length
(m)
ZR/ZT 145
4 x (3xAWG 000 + AWG 2) 2X (3X 250)
2X (3X 600)
120
ZR/ZT 160
4 x (3xAWG 000 + AWG 2) 2X (3X 250)
2X (3X 600)
120
ZR/ZT 200
4 x (3xAWG 250 + AWG 0) 2X (3X 300)
2X (3X 600)
184
ZR/ZT 250
4 x (3xAWG 300 + AWG 0) 2X (3X 350)
2X (3X 600)
207
ZR/ZT 275
4 x (3xAWG 300 + AWG 0) 2X (3X 350)
2X (3X 600)
207
Compressors designed for a maximum ambient temperature of 104 °F (40 °C) with IE3 motors
Type
FLA
MCA
Proposed cable
(mm²)
Maximum
cable
length (m)
Proposed
fuses (A)
(LPJ)
Maximum
fuse (A)
(LPJ)
SCCR
ZT/ZR 110
211
233
2 X (3 X00+4AWG)
180
2 x(3 X
150)
600
65 kA
ZT/ZR 145
273
300
2 X (3 X0000+2AWG)
208
2 x(3 X
200)
600
65 kA
ZT/ZR 160
305
336
2 X (3 X0000+2AWG)
183
2 x(3 X
225)
600
65 kA
ZT/ZR 200
365
402
2 X (3 X 300MCM
+2AWG)
149
2 x(3 X
300)
600
65 kA
ZT/ZR 250
425
468
4 X (3 X 00+4AWG)
121
2 x(3 X
300)
600
65 kA
ZT/ZR 275
502
552
4 X (3 X 000+4AWG)
114
2 x(3 X
350)
600
65 kA
FLA and MCA based on an air-cooled full option compressor.
SCCR only achieved with recommended fuses.
FLA and MCA based on an air-cooled full option compressor.
SCCR only achieved with recommended fuses.
4.5
Electric connection
Attention
For the selection of the correct cables, refer to:
Electric cable size, fuses and cable
.
Instruction book
AIF999999
61