Tightening
304
9836 3521 01
6.5.2.26 D - Diagnostic Step
Step type Id:
22
Parameters:
Function:
Defines the diagnostic checks to perform in a tightening program.
Normally the diagnostic step is the first step in a program but it can be a later step in the
program (e.g. when Flying Zero Offset is used).
The diagnostic step can also be performed in a special program, which can be run between
normal cycle programs. The normal programs will hence be faster.
The limits for PowerMACS zero offset compensations are configured using the Spindle Set
Up form.
Select if you want a
Spindle Functional Test
to be performed. This test verifies the spindle
is working correctly and adjusts the spindle‟s measuring system. This test is performed
automaticly at startup but it is recommended to run a Diagnostic step with the spindle
functional test as the first step in every tightening program to compensate torque
measurements.
The spindle takes care of zero offset compensation, if this is not sufficient you can select to
let PowerMACS
also
compensate for zero offsets using the
Static
,
Dynamic
or
Flying
method.
Check
Angle count test
to execute a test of the angle measurement channels. Chapter:
Dynamic Zero Offset and Angle Count describes how this is done.
Errors detected in a diagnostic step are reported as
Fatal
errors except for one case. If the
Flying Zero Offset parameter
Continue to run after failed check
is checked (see Spindle
Set Up), a flying zero offset error is reported as a warning instead of as an error.
Note!
The double torque transducer test is not executed while the spindle functional test is
performed or zero offset is being measured. The double angle encoder test is not executed
while the spindle functional test is performed.
Trace
:
There are no control parameters for this step type in trace.
Summary of Contents for PowerMACS 4000
Page 2: ......
Page 46: ...System Architecture 46 9836 3521 01...
Page 267: ...Tightening 9836 3521 01 267...
Page 400: ...Tightening 400 9836 3521 01...
Page 486: ...Peripheral Devices 486 9836 3521 01...
Page 622: ...Peripheral Devices 622 9836 3521 01...
Page 664: ...References 664 9836 3521 01...
Page 668: ...9836 3521 01 2010 11 Edition 10 3 0 www atlascopco com...