Reference
Name
A
Air inlet temperature in ˚C
B
Condensation temperature in ˚C
C
Effective working pressure in bar
D
Relative air humidity in %
5.4
During operation
Warning
The operator must apply all relevant
.
The operator should immediately stop the machine in case of oil leaks internally in the
machine as wel as externally and consult a competent technician to resolve the cause.
The machine should not be restarted before the problem has been remedied
Control panel
Control panel of MkIV regulator
1. When the automatic operation LED (8) is lit, the starting and stopping of the motor is controlled
automatically.
2. Check the readings on display (2).
3. To unload the compressor manually, press the “Unload” key (5). To put the compressor back into automatic
operation, press the “Load” key (5).
4. Regularly check that the vessel of the OSD is filled; if necessary, gently top up with water to the level of
the water outlet and re-install the cover
.
5. On Full-Feature compressors, regularly check the pressure dew-point on the display of the control panel.
The pressure dew-point will deviate from nominal if the air inlet conditions or volume differ from nominal.
Instruction book
84
2920 1475 06
Summary of Contents for GA110
Page 1: ...GA 90 GA 110 GA 132 GA 160 GA 200 GA 250 GA 315 ...
Page 2: ......
Page 17: ...Flow diagram of GA200 GA250 and GA315 60 Hz Instruction book 2920 1475 06 15 ...
Page 30: ...Menu flow for GA 90 up to GA 315 simplified example Instruction book 28 2920 1475 06 ...
Page 57: ...Dimension drawing of GA90 110 water cooled Instruction book 2920 1475 06 55 ...
Page 60: ...Dimension drawing of GA200 250 and GA315 60 Hz air cooled Instruction book 58 2920 1475 06 ...
Page 64: ...Compressor room example of GA 90 up to GA 160 water cooled Instruction book 62 2920 1475 06 ...
Page 76: ...Suspended solids Non soluble particles size 1 mm 10 ppm Instruction book 74 2920 1475 06 ...
Page 98: ...Filler and drain plugs on GA 200 up to GA 500 compressors Instruction book 96 2920 1475 06 ...
Page 102: ...Position of oil filter on GA 200 up to GA 500 Instruction book 100 2920 1475 06 ...
Page 133: ...Instruction book 2920 1475 06 131 ...
Page 134: ......
Page 135: ......