4. Discard the old filter element.
5. Remove the O-ring from the bowl and clean the bowl with isopropanol. Cleaning cloths of Kimtech are
recommended. Position a new O-ring on the bowl.
6. Open the sealed bag at the topcap side of the filter cartridge.
7. Take the cartridge and lower the plastic until the middle of the cartridge.
8. Position the cartridge under the filter head and push it in place.
Only touch the plactic bag. Avoid contact
of the filter cartridge with the hands
.
9. Remove the plastic bag and reposition the bowl.
A small amount of
paint compatible lubricant
( e.g . FOODLUBE EXTREME) may be applied
to screw threads and O-rings to facilitate the assembly.
7.4
Filter disposal
Used filters must be disposed of in an environmentally friendly and safe manner, and in line with the local
recommendations and environmental legislation.
7.5
Reference conditions
Air inlet pressure
7 bar(e)
Air inlet temperature
20˚C
Ambient temperature
20˚C
7.6
Principal data
Maximum compressed air inlet pressure
16 bar(e)
Minimum compressed air inlet pressure
1 bar(e)
Minimum compressed air inlet temperature
1˚C
Maximum compressed air inlet temperature
65˚C
Maximum compressed air inlet pressure
16 bar(e)
Minimum ambient temperature
1˚C
Maximum ambient temperature
65˚C
Maximum recommended pressure drop
0.35 bar(e)
Instruction book
92
APF192090
Summary of Contents for GA 160 VSD
Page 1: ...GA 160 VSD APF192090 Instruction book ...
Page 2: ......
Page 64: ...Instruction book 62 APF192090 ...
Page 66: ...Figure A Instruction book 64 APF192090 ...
Page 67: ...Figure B Instruction book APF192090 65 ...
Page 70: ...Text on figure Instruction book 68 APF192090 ...
Page 77: ...Ref Designation 29 Do not mix oil brands Instruction book APF192090 75 ...
Page 92: ...See Oil specifications Instruction book 90 APF192090 ...
Page 111: ......