![Atlas Copco GA 11 VSD+ Instruction Book Download Page 127](http://html.mh-extra.com/html/atlas-copco/ga-11-vsd/ga-11-vsd_instruction-book_3001655127.webp)
9.4
Compressor data
Reference conditions
All data specified below apply under reference conditions, see section
Common compressor data
Unit
Number of compression stages
1
Temperature of the air leaving the outlet valve (approx.), Workplace
˚C
30
Temperature of the air leaving the outlet valve (approx.), Workplace
˚F
86
Temperature of the air leaving the outlet valve (approx.), Workplace Full-
Feature
˚C
30
Temperature of the air leaving the outlet valve (approx.), Workplace Full-
Feature
˚F
86
Refrigerant type, Workplace Full-Feature
R134a
GA 7 VSD+
Normal effective working pressure
bar(e)
5.5
7
9.5
12.5
Normal effective working pressure
psig
80
102
138
181
Maximum effective working pressure,
Workplace
bar(e)
13
13
13
13
Maximum effective working pressure,
Workplace
psig
189
189
189
189
Maximum effective working pressure,
Workplace Full-Feature
bar(e)
12.75
12.75
12.75
12.75
Maximum effective working pressure,
Workplace Full-Feature
psig
185
185
185
185
Maximum motor shaft speed
rpm
5250
5250
4500
3750
Minimum motor shaft speed
rpm
1900
1900
1900
2100
Nominal motor power
kW
7.5
Nominal motor power
hp
10
Total amount of refrigerant, Workplace Full-Feature
kg
0.4
Total amount of refrigerant, Workplace Full-Feature
lb
0.88
Oil capacity
l
6.5
Oil capacity
US gal
1.72
Oil capacity
Imp. gal
1.43
Oil capacity
cu. ft.
0.23
Sound pressure level (according to ISO 2151 (2004))
dB(A)
62
Instruction book
2920 7109 23
125