51
Backup TIME & Battery
Backup Time
A03-P841
23'
14'
9'
5'
2':30"
1':30"
Power Rating(W)
115
170
240
300
360
480
Power Rating(VA)
230
340
480
600
720
960
Backup Time
A03-P701
19'
11'
7'
5'
3'
2'
Power Rating(W)
115
170
230
285
320
360
Power Rating(VA)
230
340
460
570
640
720
A03- P701/841
Battery Low
11.0V ± 0.5VDC
Battery CutOFF
10.0V ± 0.5VDC
Battery Charging Voltage
13.8V ± 0.4VDC
AVR
Vin(V)
AVR
Vout(V)
Note
Vin
≦
162V
N/A
Inv (220± 10%)
the UPS returns to AC
output mode when AC
input increase to 168V
162V
≦
Vin
≦
200V
YES
Boost
201V
≦
Vin
≦
239V
N/A
Vin
240V
≦
Vin
≦
268V
YES
Buck
Vin
≧
268V
N/A
Inv (220± 10%)
The UPS returns to AC
output mode when AC
input drops to 262V