3.6 Operating Mode Description
Mode
LCD
Description
Online
Mode
When the input voltage is within
acceptable range, UPS will
provide pure and stable AC power
to output. The UPS will also
charge the battery at online
mode.
ECO mode
Energy saving mode:
When the input voltage is within
voltage regulation range, UPS will
bypass voltage to output for
energy saving.
AECO
Mode
When the input voltage is within
setting range (±3%Vo max), UPS
will bypass voltage to output for
energy
saving.
PFC
and
INVERTER are off at this mode.
Fhz
Converter
Mode
When input frequency is within 40
Hz to 70 Hz, the UPS can be set
at a constant output frequency,
50 Hz or 60 Hz. The UPS will still
charge battery under this mode.