Model denomination alféa hybrid duo gas
11
14+
11 three
14 three
16 three
Domestic hot water tank
Capacity of domestic hot water tank
litre
120
Max DHW circuit usage pressure (PMS)
MPa (bar)
0.7 (7)
Specific DHW flow rate at DT 30°K (D)
l/mn
20
Max temperature
°C
65
Miscellaneous
Weight of the outdoor unit
kg
92
99
Weight of the hydraulic module (empty/with water)
kg
135 / 278
Hydraulic module water capacity
litre
23
Acoustic power
(5)
according to EN12102
(hyd. module: thermodynamic mode)
dB (A)
46
Noise level
(4)
at 5 m (outdoor unit)
dB (A)
47
48
44
46
47
Acoustic power
(5)
in compliance with EN 12102 (outdoor unit)
(water range 45 ° C to NF PAC)
dB (A)
69
70
66
68
69
Heating operating limits
Min./max. outdoor temp. (thermodynamic mode)
°C
-25 / +35
Max. water temperature (thermodynamic mode)
°C
60
Max. flow water temperature for start of heating
°C
80
Gas boiler characteristics
Gas flow rate in continuous operation
(15°C - 1013 mbar)
- Natural gas (G20 - 20 mbar)
m
3
/h
2.55
- Natural gas (G25 - 25 mbar)
m
3
/h
2.93
- Propane (G31 - 37 mbar)
m
3
/h
1.00
Diaphragm
(gas valve outlet)
- Natural gas (G20 - 20 mbar) item - diameter
item - Ø
20 - 6.5 mm
- Natural gas (G25 - 25 mbar) item - diameter
item - Ø
none
- propane (G31 - 37 mbar) item - diameter
item - Ø
conical - 3.9 mm
Combustion products
Smoke temperature (minimum / maximum)
°C
35 / 70
Smoke mass flow rate (minimum / maximum)
g/s
2.87 / 11.9
Concentric horizontal or vertical room sealed ( turbo ) pipe
Smoke / air aspiration tube diameter (C13, C33)
mm
80 / 125
Smoke tube diameter (C53)
mm
80
Maximum authorised straight line length (excluding terminal)
m
11
Loss of charge by elbow (90° / 45°)
m
1 / 0.5
Compatible terminal and material
UBBINK
(6)
With chimney adaptor
Smoke tube diameter
mm
80
Optimum low pressure in the chimney (type B23)
Pa
15
Max. pressure available on the evacuation nozzle (type B23P)
Pa
70
(1)
Refrigerant R410A in compliance with standard NF EN 378.1.
(2)
Factory charge of refrigerating fluid R410A.
(3)
Taking into account the potential additional charge of refrigerating
fluid R410A (see
(4)
Sound pressure level at (x) m from the appliance, 1.5 m from the
ground, free field, directivity 2.
(5)
The acoustic power is a measurement made in the laboratory of the
power of the noise emitted but contrary to the noise level, it does not
correspond to the measurement of what is felt.
(6)
:
This
appliance is certified (and its operation is
guaranteed) with only the room sealed (turbo) pipe
described below:
•
Ubbink supplies
-
UBBINK ROLUX CONDENSATION GAS with polypropylene
(PPTL) internal pipe.
-
ROLUX vertical terminal 80/125 - 4 G or 5G.
-
ROLUX CON HR vertical terminal FV80/125.
-
Rénolux system for adaptation to the existing evacuation pipe.
The use of aluminium connection pipes is prohibited .
Installation and commissioning instructions "1485 - EN"
- 7 -
Heat pump alféa hybrid duo gas
Summary of Contents for WOYG112LHT
Page 51: ... Installation and commissioning instructions 1485 EN 51 Heat pump alféa hybrid duo gas ...
Page 69: ... Installation and commissioning instructions 1485 EN 69 Heat pump alféa hybrid duo gas ...
Page 90: ...Installation and commissioning instructions 1485 EN Heat pump alféa hybrid duo gas 90 ...
Page 91: ...Installation and commissioning instructions 1485 EN 91 Heat pump alféa hybrid duo gas ...