6 .5
Configuring room thermostat
(T55 or T58)
To configure the ambient sensor and associate it to the
adequate heating zone:
-
Hold down the presence button for over 3s.
The room thermostat displays RU and a figure flashes.
-
Turn the knob to select the zone (1 or 2):
"
If the installation has a single radiator circuit,
zone 2 is active (CC2).
"
If the installation has 2 ambient sensors,
Connect a sensor to X86 (RVS) first and
configure it in zone 2.
Then connect the other sensor which is
configured by default in zone 1.
-
Press the presence button, the ambient
sensor displays P1 and a figure flashes.
1: Automatic storing; a correction of the value with
the knob is adopted without any specific validation
(timeout) or by pressing the operation button.
2: Save with confirmation; a correction of the value with
the knob is only adopted after pressing the operation
button.
-
Press the presence button again, the ambient sensor
displays P2 and a figure flashes.
0 : OFF; all of the operating elements are available.
1 : ON; the following operating elements are locked:
- Switching the operation mode of the heating
circuit
- Adjusting the comfort value.
- Changing the operating level.
The ambient sensor displays OFF for 3s when a locked
button is pressed.
6 .6
Configuration of the room control unit
(T75 or T78)
When putting into service, after a reset of around
3 minutes, the user language needs to be set:
-
Press
OK
-
Select the "user Interface" menu.
-Select the language
Select the language (
English
, Deutsch, Français,
Italiano, Nederlands, Español, Português, Dansk).
"
If the installation has a single radiator circuit,
zone 2 is active (CC2).
"
In the case of 2 heating circuits:
-
Choose the central ambient unit's assignment
(ambience appliance 1 or 2, etc.) line
40*
).
-
Depending on the assignment selected, check and
modify if necessary the settings of lines
42*
,
44*
,
48*
).
Line
Function
Setting range or display
Setting
increment
Basic setting
40
I
Use as...
Ambience appliance 1, 2, P,
User interface 1, 2, P,
Service appliance
Ambience
appliance 1
This line is used to set the use of the central ambient unit. Depending on use, other settings are necessary (lines 42,
44, 48)
42
I
Assignment appliance 1
Heating circuit 1,
Heating circuits 1 & 2,
Heating circuits 1 & P,
All heating circuits
Heating
circuit 1
44
I
Operation heating circuit 1 (heating circuit 2
command)
Common with heating circuit 1,
Independent
Common
with heating
circuit 1
This function permits the choice to be made if the ambient sensor (in option) has an action on the two zones or on a
single zone.
48
I
Presence button action
None,
Heating circuit 1,
Heating circuit 2,
Common
* These parameter lines are only accessible from the central ambient unit.
Installation and commissioning instructions "1485 - EN"
Heat pump alféa hybrid duo gas
- 50 -
Summary of Contents for WOYG112LHT
Page 51: ... Installation and commissioning instructions 1485 EN 51 Heat pump alféa hybrid duo gas ...
Page 69: ... Installation and commissioning instructions 1485 EN 69 Heat pump alféa hybrid duo gas ...
Page 90: ...Installation and commissioning instructions 1485 EN Heat pump alféa hybrid duo gas 90 ...
Page 91: ...Installation and commissioning instructions 1485 EN 91 Heat pump alféa hybrid duo gas ...