Atlantic WOYA 060 LFCA Installation Manual Download Page 1

Installation manual

for professionals

to be kept by the user

for future reference

Loria duo 6000

atlantic-comfort.com 

Air/water heat pump

split, 2 services

Outdoor unit

Hydraulic unit

WOYA 060 LFCA

023010

WOYA 080 LFCA

023011

WOYA 100 LFTA

FR NL DE EN PL

ES PT

IT

PT PT

U0577305_1715_EN_10 

11/04/2018

Summary of Contents for WOYA 060 LFCA

Page 1: ...by the user for future reference Loria duo 6000 atlantic comfort com Air water heat pump split 2 services Outdoor unit Hydraulic unit WOYA 060 LFCA 023010 WOYA 080 LFCA 023011 WOYA 100 LFTA FR NL DE EN PL ES PT IT PT PT U0577305_1715_EN_10 11 04 2018 ...

Page 2: ... refrigerants Circulation pump operation 39 Floor drying mode 39 Refrigerant connection and filling the installation with gas 19 Rules and precautions 19 Shaping the refrigeration pipes 19 Checks and connections 20 Filling the installation with gas 22 Additional charge 25 Collecting refrigerant in the outdoor unit 25 Hydraulic connections 26 Rinsing the installation 26 Connections 26 Connecting to...

Page 3: ...tic hot water tank 53 Checking the outdoor unit 53 Electrical checks 53 Maintenance 54 Accessing the electric box 54 Replacing fuses 54 Electrical wiring diagrams 56 Instructions for the user 65 Electrical wiring outdoor unit 56 Quick start procedure 62 Commissioning check list 62 Settings sheet 64 Start up data sheet 65 Draining the hydraulic unit 54 ERP performance values 66 ERP definition 66 ER...

Page 4: ...2 or Black rubber floor support ref 809 536 Condensate drain pan ref 074 008 Container bottom tracer ref 809 644 Scope This heat pump provides Heating in winter Control of two heating circuits Production of domestic hot water provided that combined with a DHW tank Cooling in summer for floor heating cooling system or fan coil unit These options require the use of additional kits see Optional equip...

Page 5: ...door unit W 49 Maximum power absorbed by the outdoor unit W 2530 2875 4025 4255 Rates as per EN14825 0 0120 0 0074 0 0057 Hydraulic circuit Maximum pressure for heating DHW MPa bar 0 3 3 1 10 Available heating pressure at nominal point 7 C 35 C MPa bar 0 064 0 64 0 05 0 5 0 036 0 36 0 021 0 21 Minimum allowed hydraulic flow rate l h 420 600 Min max hydraulic system flow rate 4 C Δt 8 C nominal con...

Page 6: ...ns of the hydraulic unit see page 18 Side view D1 Heating outgoing flow area 1 ø M 26x34 R1 Heating return flow area 1 ø M 26x34 D2 Heating outgoing flow optional area 2 ø M 26x34 R2 Heating return flow optional area 2 ø M 26x34 DCW DCW inlet ø DHW DHW outlet ø G Gas refrigeration connection ø 5 8 L Liquid refrigeration connection ø 3 8 Installation manual 1715 EN Loria duo 6000 heat pump 6 ...

Page 7: ... AIR AIR 4 holes Ø11 Outdoor unit Loria duo 6004 6006 and 6008 models Installation manual 1715 EN 7 Loria duo 6000 heat pump figure 2 Dimensions of the outdoor unit in mm 650 AIR AIR 370 830 21 196 99 9 900 77 12 330 31 147 170 400 Outdoor unit Loria 6010 model ...

Page 8: ...it Outdoor sensor C 0 5000 10000 15000 20000 25000 30000 35000 0 10 20 30 40 50 60 70 80 90 100 B3977 10 kΩ 25 C HP return sensor HP outgoing sensor Outdoor sensor QAC2030 NTC 20 10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 10000 1000 100 10 1 Compressor Discharge Condensation Outdoors Temperature C Ohmic value kΩ Evaporator outlet Evaporator centre Compressor casing Installation manual 1715 EN...

Page 9: ...der 6 4 way valve 7 Panels treated against corrosion 8 Electronic expansion valve of the main circuit 9 Inverter compressor acoustically and thermally insulated 10 Refrigeration connection valves flared connectors with protective caps 11 Holding tank with condensate drain hole 12 High performance exchange surface evaporator anti corrosion treated hydrophilic aluminium blades and grooved copper tub...

Page 10: ...low combined circuit Z 2 8 Domestic Cold Water inlet 9 Domestic Hot Water outlet 10 Gas refrigeration connection 11 Liquid refrigeration connection 12 Safety valve 13 Automatic air bleeder 14 Removable expansion vessel 15 Condenser exchanger 16 Electrical back up 17 Sediment trap with filter 18 Valves 19 Pressure gauge 20 Bleed tap 21 Flow meter 22 DHW electrical backup 23 Anode 24 Reset button ov...

Page 11: ... Installation manual 1715 EN 11 Loria duo 6000 heat pump ...

Page 12: ...dependent setpoint The hydraulic unit is equipped with an electrical back up system which is designed to provide additional heat during the coldest periods Regulation functions The initial temperature of the heating circuit is controlled by the weather dependent setpoint The power of the outdoor unit is modulated according to the need via the inverter compressor Control of the electrical back up A...

Page 13: ...ectrical back up system inside the tank To ensure that the DHW setpoint is reached the electrical back up system must be left on DHW production takes priority over heating nevertheless the production of DHW is controlled by cycles that control the times assigned to the heating and the production of DHW in the event of simultaneous demand A DHW boost function is available on the user interface user...

Page 14: ... not be in a horizontal position during transport Transport in a horizontal position may damage the appliance by moving the refrigerant and damaging the compressor s suspensions Damage caused by transportation in a horizontal position is not covered by the warranty If necessary the outdoor unit may be tilted during manual handling to go through a door or use a staircase This operation must be cond...

Page 15: ...is 5 m for correct operation The appliance s warranty will become void if it is applied with cooling connections that are shorter than 5 m tolerance 10 If the refrigeration connections are exposed to weathering or UV rays and the insulation is not UV resistant protection must be provided 8 7 6 6 Outdoor sensor to monitor the outdoor temperature 7 Adapter 1 2 5 8 and or 1 4 3 8 to connect the flare...

Page 16: ...rainage pipe can also be connected to the outdoor unit see page 17 Nothing should obstruct the air from circulating through the evaporator and out of the fan Keep the outdoor unit away from sources of heat or inflammable products Ensure that the appliance does not disturb neighbours or users noise level draughts caused low temperature of the air blown causing a risk of freezing plants in its path ...

Page 17: ...13 The outdoor unit can generate a large volume of water called condensate If an evacuation pipe must be used Install the condensate drain pan BR optional see page 4 Use the elbow provided C and connect a hose of 16 mm diameter to discharge the condensates Use the plug s supplied B to plug the orifice of the condensate drain pan Provide for the gravitational discharge of the condensates waste wate...

Page 18: ...9 kg m The opening between the two rooms must have a door clearance of at least 1 cm or that the location is mechanically ventilated Be careful to keep the heat pump away from inflammable gas during installation in particular when it requires brazing The appliances are not fireproof and should therefore not be installed in a potentially explosive atmosphere To avoid condensation inside the condens...

Page 19: ...vel of humidity around the refrigerating pipes could exceed 70 protect the latter with insulating sleeves Use an insulating material thicker than 15mm if the humidity level reaches 70 80 and an insulating material thicker than 20mm if the humidity level exceeds 80 If the recommended thicknesses are not complied with under the conditions described above condensation will form on the surface of the ...

Page 20: ...by hand without much force being required Depending on the case connect an adapter reducer 1 4 3 8 or 1 2 5 8 see figure 18 page 21 Comply with the indicated tightening torques figure 17 The refrigeration circuit is very sensitive to dust and humidity check that the area around the connection is clean and dry before removing the caps protecting the refrigeration connectors Blowing indicator value ...

Page 21: ...n manual 1715 EN 21 Loria duo 6000 heat pump Heat pump model Loria duo 6004 6006 Loria duo 6008 Loria duo 6010 gas liquid gas liquid gas liquid Outdoor unit connections 1 2 1 4 5 8 1 4 5 8 3 8 Refrigerating connections Diameter D1 1 2 D2 1 4 D1 5 8 D2 1 4 D1 5 8 D2 3 8 Minimum length L 5 Maximum length L 15 Maximum length L 30 Maximum level difference D 20 Male female adapter reduction R1 1 2 5 8 ...

Page 22: ...E MH Liaison liquide gaz Haute pression Azote Nitrogen Gas pressure High Connection Liquid HU OU c Reconnect the hose to the vacuum pump turn on and gradually open the hose valve Lo Hi UE MH Liaison liquide gaz Haute pression Connection Liquid Gas pressure High HU OU d Repeat this operation at least three times Reminder it is strictly forbidden to perform these operations with the refrigerant If t...

Page 23: ...ssion Azote 10barsmax 30 mn mini Connection Liquid Gas pressure Nitrogen 10 bars max 30 mn min High HU OU Search for leaks with a leak detector product repair and repeat the test Lo Hi UE MH Liaison liquide gaz Haute pression Contrôle d étanchéité Vanne fermée Contrôle pression Dichtheidscontrole pressure High bij 1 bar HU OU When the pressure is stable and any leakage is excluded empty the nitrog...

Page 24: ...l valve fully and then the gas valve large valve using a hex Allen key counter clockwise direction without forcing excessively against the stop Quickly remove the hose from the Manifold Refit the 2 original caps ensure that they are clean and tighten them to the recommended tightening torque as shown in the table figure 17 page 20 The seal is produced in the caps via a metal on metal contact only ...

Page 25: ...nsure that all electrical power supplies have been cut off before starting work Stored energy after disconnecting the power supplies wait 1 minute before accessing the internal parts of the equipment Perform the following procedures to collect the refrigerant Ensure that the pressure gauge kit Manifold has been previously installed 1 Power off the appliance and its peripherals hydraulic unit outdo...

Page 26: ...ctions The heating circulating pump is built into the hydraulic unit The diameter of the pipe between the hydraulic unit and the heating manifold must be at least equal to 1 inch 26x34 mm Tightening torque 15 to 35 Nm Water volume To maintain a comfortable level for the user please comply with the minimum water volume per circuit see table 1 3 page 4 Circuit equipped with dynamic radiators a buffe...

Page 27: ...rn of 2 circuits DynR or FC DynR or FC MH 10 15 20 25 30 a a b b c A B figure 24 Connecting the floor heating system a Area controlled by thermostat on valve and room thermostat a Area controlled by thermostat on valve and remote control c Area controlled by the HP A Bypass B Open loop Bypass or Open Loop mandatory for each area 4 5 Connecting to the DHW circuit The dielectric function is produced...

Page 28: ...t Key BT Buffer Required if the installation s volume is less than the recommended volume see page 4 Mandatory with Rdyn C Circulation pump Déc Sediment trap with filter MH Hydraulic unit PC Floor heating system R Radiator Rdyn Dynamic radiator SA Room sensor optional except with Rdyn SE Outdoor sensor SP Thermal safety device for floor heating system Installation manual 1715 EN Loria duo 6000 hea...

Page 29: ... volume is less than the recommended volume see page 4 Mandatory with Rdyn C Direct circuit circulation pump CCM Mixed circuit circulation pump Déc Sediment trap with filter K2C 2 area kit MH Hydraulic unit PC Floor heating system R Radiator Rdyn Dynamic radiator SA1 SA2 Circuit 1 circuit 2 room sensor optional except with Rdyn SE Outdoor sensor S DpM Mixed circuit initial flow sensor SP Thermal s...

Page 30: ...nder a nominal voltage of 230 V 10 50 Hz 5 1 2 Electrical connections It is essential to maintain the phase neutral polarity when making the electrical connections Rigid wires are preferable for fixed installations particularly in a building see page 31 Clamp the cables using cable clamps to avoid any accidental disconnection of the conductive wires Tightening torque 0 4 to 0 6 N m Ø 15 max 1 2 4 ...

Page 31: ...ps Loria duo 6004 6006 6008 Power supply to the electrical back ups Model Power Nominal current Cable 1 phase neutral earth Curve C circuit breaker size Back up DHW 1600 W 7 A 3 x 1 5 mm 2 16 A Heating back up 3000 W 13 A 3 x 1 5 mm 2 16 A 1 Cable type 60245 IEC 57 or 60245 IEC 88 2 Note The cable used to connect the electrical back up must not exceed 3 x 2 5 mm the spring terminal cannot receive ...

Page 32: ...mentation générale Make the connections according to the diagram figure 27 Use cable clamps to prevent the conductors from being disconnected accidentally Déposer le capot 2 vis Crochets 4 endroits Câbles Serre Câble Installation manual 1715 EN Loria duo 6000 heat pump 32 Loria duo 6010 model Remove the front panel remove the cover Remove the cap 1 screw Brackets 4 places Remove the front panel 2 ...

Page 33: ...t panel 2 screws Ø 13 Rotate the electric box 2 screws figure 30 page 33 figure 29 Removing the front panel 13 2 3 1 U0531788 A Power terminal block LV LV cable bushing power SELV cable bushing sensors Sensor terminal block SELV A B A figure 30 Access Installation manual 1715 EN 33 Loria duo 6000 heat pump ...

Page 34: ...layed to create equivalent wiring In all cases please refer to the instruction manuals for the external components load shedder etc to create the wiring L N 11 12 13 230 V L N 4 5 6 7 8 9 10 COM EX1 EX2 EX3 L N 1 2 3 230 V figure 32 LV cable bushing LV raceway LV terminal block Do not place the sensor lines and the sector supply lines in parallel in order to avoid interferences due to voltage poin...

Page 35: ...In particular domestic hot water DHW at Nominal temperature will be produced during the off peak hours when electricity is cheaper Connect the energy supplier contact to input 9 Rates EX2 Load shedding or peak shaving The purpose of load shedding is to reduce the electrical consumption when it is too high compared to the contract with the energy supplier Connect the load shedder to input 8 Load Sh...

Page 36: ...e but at least 2 5 m from the ground Avoid sources of heat such as chimneys the tops of doors or windows nearby extraction ducts underneath balconies and porches that would insulate the sensor from the variations in the temperature of the outside air Connect the outdoor sensor figure 34 SELV raceway Comply with the safety distances between SELV and LV power cables Ensure that all of the electrical...

Page 37: ... areas exposed to draughts ventilation doors Draughts due to the building usually cause cold air to enter via the electrical ducts Seal the electrical ducts if there is a cold draught at the back of the room thermostat Connect the room thermostat 1 figure 34 Connect the room thermostat 2 figure 34 5 2 3 Telephone modem optional Connect the telephone control outlet to the modem terminals see figure...

Page 38: ...n put into service and every time that the main circuit breaker is cut off then reconnected the outdoor unit requires approximately 3 minutes to start up even if the regulation has demanded heating While the regulator is being initialised the display shows all icons Note When starting up the heating function after the HP has been fully shut down and for a heating network temperature not exceeding ...

Page 39: ...rotective sheathing O ring seal Magnet Magnetic catch cover figure 37 Cleaning the sediment trap 6 4 Circulation pump operation The speed of the heating circulation pump can be adjusted via the user interface see Circulation pump page 46 By default the pump is set to the maximum speed speed 4 Circulation pump errors When error Er 76 is displayed check all components that may block the hydraulic fl...

Page 40: ... information menu the icon appears Exit the menu currently displayed Cancel a modification being made 5 Configuration Access the user level press and release the icon appears Access the installer level press and hold for more than 5s the icon appears List of parameters see 7 4 4 page 44 6 OK Confirm Configuration Setpoint for the pre selected mode 7 Display Display see Description of the display u...

Page 41: ...lectric power supply to the HP is not switched off Description of the display room thermostat C 00 00 0 0 0 BOOST 1 2 3 4 5 6 7 1 2 3 4 5 6 OUT Icons Definitions Heating indicator DHW indicator Cooling indicator Current configuration BOOST Exemption Heating or DHW Absence mode 0 0 0 Display Temperature Setpoint value Error codes OUT Outdoor indicator temperature 18 30 Time display 1 2 3 4 5 6 1 2 ...

Page 42: ... 20 70 60 50 40 30 20 1 0 75 0 5 0 25 1 25 Heating curve slope Heating flow temperature C Outdoor temperature C Dynamic radiators Low temperature radiator Floor heating system figure 39 Heating curve displacement line 31 51 40 50 60 70 20 15 10 5 5 10 4 5 4 5 20 0 10 30 0 30 Heating start temperature C Outdoor temperature C Displacement Weather dependent setpoint slope 0 5 The weather dependent se...

Page 43: ...se OK OK Press and hold 5s Display installer level Select parameter Confirm Select value Confirm Back to basic display OK OK 7 4 3 Recommended settings for the parameters depending on the installation s transmitters Heating VLT Radiators Heating cooling floor Low temperature radiators Classic temperature radiators Dynamic radiators or fan coil heaters Heating curve slope 30 CC1 0 25 to 0 5 0 5 to ...

Page 44: ...ment of the temperature setpoint used during absence mode Heating time programme 2 circuit 1 direct 11 Pre selection day week 1 10 1 Monday 2 Tuesday 7 Sunday 8 Monday to Friday 9 Saturday and Sunday 10 Monday to Sunday modifications are applied to the whole week 12 1st phase of the selected day start of comfort 00 00 23 45 06 00 13 1st phase of the selected day end of comfort 00 15 24 00 22 00 14...

Page 45: ...tion enables you to choose the ambient temperature s influence on the setting If no value is entered only the weather dependent setpoint is configured 34 Parameter not used 0 not used 1 on 1 35 Zone 1 emitter type 0 Radiator 1 Underfloor heating 0 36 Accelerated lowering 0 off 4 0 C h This function enables you to force the heating to stop when the temperature setpoint is lowered The time the heati...

Page 46: ...n the exterior temperature is higher than the setpoint 1 C Cooling setting 1 circuit 2 combined 61 Cooling curve slope 0 1 4 00 0 7 62 Cooling curve displacement 4 5 4 5 C 0 63 Min initial cooling setpoint 5 30 C 10 C Circulation pump 70 Pump speed 1 4 4 Heat pump 71 Heating standby switchover authorisation 0 manual 1 automatic 1 72 Automatic change in state according to the outdoor temperature he...

Page 47: ... initial constant heating setpoint for each circuit The room thermostat must be disconnected for this mode to work The parameter must be set to Off to deactivate the floor drying mode 95 DHW forced operation DHW boost 0 off 1 on 0 96 Appliance test 0 9 This parameter is used to test the components connected to the controller It is used to check that the relays are operating and that the wiring is ...

Page 48: ...Wh 32 Heat Energy consumed this year MWh 33 Heat Energy consumed last year MWh 40 Cool Energy consumed this month kWh 41 Cool Energy consumed last month kWh 42 Cool Energy consumed this year MWh 43 Cool Energy consumed last year MWh 50 DHW Energy consumed this month kWh 51 DHW Energy consumed last month kWh 52 DHW Energy consumed this year MWh 53 DHW Energy consumed last year MWh Status list No Va...

Page 49: ...cut off Defective sensor Other error 132 Initial temperature 70 C T5 46 Circuit 2 sensor error T12 Short circuit sensor disconnected or cut off Defective sensor Other error 48 Outdoor temperature sensor error T7 Short circuit sensor disconnected or cut off Defective sensor Other error 47 DHW tank sensor error T8 Short circuit sensor disconnected or cut off Defective sensor Other error 148 Legionel...

Page 50: ...arameter 33 used without room unit Room unit disconnected or absent 69 Room temperature in area 2 missing when the room T influence function No 53 is activated Parameter 53 used without room unit Room unit disconnected or absent 70 Assist mode activated 71 Circuit temperature 2 55 C Defective mixing valve 73 External error linked to input EX3 Parameter 75 set to 1 HP locked Outdoor component error...

Page 51: ...ressure regulator temperature sensor error 13 8 Flashes 4 Flashes Current current error 14 8 Flashes 6 Flashes 3 Flashes Pressure sensor error pressure switch error 15 9 Flashes 4 Flashes 13 Flashes Current sensor error permanent shutdown 16 9 Flashes 5 Flashes 14 Flashes Detection error for the position of the compressor rotor permanent shutdown 15 Flashes Compressor start up error permanent shut...

Page 52: ... trap For detailed information see 6 3 page 39 9 2 2 Annual inspection Check the heat output assessment with the temperature deviation outgoing return and flow rate Warning If frequent refills are required it is essential that you look for any leaks If you need to fill up and reset the pressure check the type of fluid originally used Recommended filling pressure between 1 and 2 bar the exact filli...

Page 53: ...k the wear on the anode the anode gradually dissolves depending on the quality of the supply water thus preventing tank corrosion Replace the anode if its diameter is less than 13 mm Replace the seal around the inspection trap ref 4 every time the inspection trap is dismantled Reinstall the inspection trap and tighten the bolts in the criss cross pattern Reconnect the electrical back up Reassemble...

Page 54: ...figure 46 or 11 2 page 60 Fuse properties T3 15AH250V 5x20 mm IEC 60127 1 T6 3AH250V 5x20 mm IEC 60127 1 10 3 Draining the hydraulic unit Set the distribution valve to the intermediary position set parameter 96 Appliance test to 10 Open the drainage valve ref 5 Open the hydraulic unit s automatic bleeders ref 6 Open the installation s air bleeder B C C D1 C E Hand the assembly on the screw of the ...

Page 55: ... Installation manual 1715 EN 55 Loria duo 6000 heat pump ...

Page 56: ...BK RD BU OG YE WH BK BK BK BK BK BK BK BK WH WH WH WH RD RD BN BN OR BK BK WH RD WH RD BK BK GN GN Vanne 4 voies Ventilateur Détendeur électronique Compresseur Réactance Réactance Sonde température Evaporateur Sonde température Détendeur électronique Sonde température Refoulement Sonde température Compresseur Capteur Pression Sonde température Extérieur Bornier Interconnexion entre unité extérieur...

Page 57: ...3 2 1 CM PS 4WV PMV FM Main PWB IPM PWB Filter PWB ACTPM WH WH WH WH WH WH WH WH WH WH WH WH WH WH WH BK BN RD OG YE RD WH BK BN BN BK BK BK BK BK BK BK BK BK BK WH YE OG BU RD BN YE WH BK RD RD RD WH WH RD WH BK BK BN OG VT WH BU YE BK BK GN GN WH BK WH WH WH WH BK BK GY Capacitor PCB Coil Compressor Terminal block Power card IPM card Power supply Interconnection between the outdoor unit and the ...

Page 58: ...CN800 CN700 CN500 CN63 CN65 1 2 3 1 2 3 CN72 CN62 CN64 CN90 N L 3 2 1 CM 4WV PMV FM PS WH WH WH WH WH WH WH WH WH WH WH WH WH WH WH BK BN RD OG YE RD WH BK BN BN BU BU BK BK BK BK BN BN BK BK WH YE OG BU RD BN YE WH BK RD RD RD WH WH RD WH BK BK OG OG BN OG VT WH BU YE BK BK GN WH BK WH BK WH WH BK BK GY Bornier Fusible 250V 25A Capteur de pression Bobine Compresseur Posistor Condensateur PCB Cart...

Page 59: ... Installation manual 1715 EN 59 Loria duo 6000 heat pump ...

Page 60: ... mm IEC 60127 1 FUSE 250V 3 15A FUSE 250V 3 15A Sensors terminal block Electric box 2nd circuit Flow meter Return sensor Flow sensor Fuse specifications Bornier sondes Coffret électrique Caractéristiques fusibles 2ème circuit Débitmètre Sonde Retour Sonde Départ U0525670 Connection to the sensor terminal block page 36 Power operator Connection see page 35 11 2 Electrical wiring hydraulic unit excl...

Page 61: ...ng back up relay Heating electrical back up Back up DHW thermostat Heating back up thermostat Bornier alimentation Coffret bornier alimentation Relais appoint sanitaire Relais appoint chauffage Appoint électrique chauffage Thermostat appoint ECS Thermostat appoint chauffage Connections to the main terminal block page 34 Colour codes BK Black BN Brown BU Blue GN Green GY Grey OG Orange RD Red VT Vi...

Page 62: ...n connections and checks see section 3 Refrigerant connection and filling the installation with gas page 19 3 4 Filling the installation with gas page 22 OK Non compliant Refrigerant circuit check plugged no dust or moisture Connections between units pipe length flare tightening torque HP pressure gauge installation and vacuo on fluid line small tube Pump down mandatory Leak test with nitrogen 10 ...

Page 63: ... few minutes measure the difference in air T Condensation and evaporation pressure temperature check Hydraulic unit checks OK Non compliant Value After 15 minutes of operation Difference in primary water T Operation of heating mixing valve electrical back up Controller see section 7 Controller page 40 OK Non compliant Settings manipulations checks Set the scheduled periods for heating HC1 HC2 1 11...

Page 64: ... pump speed Parameter Name Settings Domestic hot water 73 Legionella cycle 95 DHW forced operation boost 25 29 time programmes Energy counting 80 EU reference power see page 47 Miscellaneous 10 Absence mode setpoint 72 switch between winter summer 74 correct outdoor temperature sensor 75 behaviour of the appliance when suffering from an external error 76 rates mode 77 direction of action input 8 L...

Page 65: ...Domestic hot water tank type Secondary network water volume estimate L Options accessories Power supply for electrical back up Room thermostat Location of room sensor correct dual circuit kit DHW kit Cooling kit Details Control settings Type of configuration Key parameters Explain to the user how the installation operates in particular the functions of the room thermostat and the programmes access...

Page 66: ... 185 131 190 132 170 128 158 120 Annual energy consumption Qhe kWh 1884 2708 2588 2933 3226 4197 4481 5256 Average climate domestic hot water production Declared load profile L L L L Energy class A A A A Energy efficiency ƞwh 130 130 130 130 Annual energy consumption AEC kWh 966 966 966 966 Daily electricity consumption Qelec kWh 4 4 4 4 Colder climate Space heating characteristics Rated heat outp...

Page 67: ...1 54 2 20 1 60 For air to water heat pumps temperature operating limit TOL C 10 10 10 10 10 10 10 10 Water temperature operating limit WTOL C 55 55 55 55 55 55 55 55 Supplementary heater Rated heat output 2 Psup kW 0 8 1 1 1 1 0 7 0 6 1 8 1 6 1 3 Type of energy input Electricity Power consumption in modes other than active mode Off mode POFF kW 0 009 0 009 0 009 0 007 Thermostat off mode PTO kW 0 ...

Page 68: ...in may not correspond to its actual energy efficiency once installed in a building as this efficiency is influenced by other factors such as heat loss in the distribution system and the dimensioning of the products in relation to the size and characteristics of the building Range 55 C A A G F E D C B A A 30 30 34 36 75 82 90 98 125 150 Product name Loria duo 6004 Loria duo 6006 Loria duo 6008 Lori...

Page 69: ... Installation manual 1715 EN 69 Loria duo 6000 heat pump ...

Page 70: ... appliance conforms to the low voltage directive 2014 35 UE under standard EN 60335 1 EN 60335 2 40 EN 60529 and EN 60529 A2 IP the electromagnetic compatibility directive 2014 30 UE the machinery directive 2006 42 EC the directive for pressurised equipment 2014 68 UE the eco design directive 2009 125 EC the energy labelling directive 2010 30 EC This appliance also complies with decree No 92 1271 ...