7. Air connecJon
Overview
InstallaBon
OperaBon
Maintenance
Warranty
If the volume of the installaBon room is not sufficient the water heater can be connected to ducts with a
diameter 160 mm. If the ducts are not insulated this could generate condensaBon in the ducts during
operaBon.
The use of insulated ducts is mandatory.
If the water heater is ducted the parameter sejng has to be adapted.
The total pressure drop of ducts and accessories for air intake and exit has to be less than 150 Pa.
The recommended length of ducts has to be respected.
PosiJon of the air intake and exit.
❶ Unscrew the fixing
s c r e w s o f t h e a i r
connecBon, then turn in
the required direcBon.
❸ Rotate again by
120°, posiBon to the
opposite sides.
❷ Rotate by 120°,
posiBon to the rear.
A poor duct installaBon (duct compressed, length or number of bends too high…) can reduce the
performance.
The ducts can be fiTed
directly on the rotaBonal
air in-‐/outlets.
EXIT
ENTRY
Note :
The
rotaBonal
air ons allow to reduce or avoid the duct bends. For further on on the
rotaBonal
air ons, see the § « Posi+oning of the water heater ».
❹ Do not posiBon the
air connecBon parBally
face to face.
PosiBon not allowed as
cold air will be recycled !
J
J
L
Number of bends 90°
Total duct length with air intake and exit (ATL catalogue)
ALUMINIUM SEMI RIGID PEHD
;;;;;;;;;;;;;;
0
8m
19m
1
7m
16m
2
5m
12m
18