Line
Function
Setting range
or display
Setting range
or display
Basic
setting
Domestic hot water
If the installation is fitted with the DHW kit.
1610
U
Nominal setpoint
Reduced setpoint (line 1612)…
65 °C
1 °C
55 °C
The electrical back-up system is required to reach this level
1612
U
Reduced setpoint
8 °C
Nominal setpoint (line 1610)
1 °C
40 °C
Swimming pool (Only with swimming pool kit option)
2056
U
Pool setpoint producer heating
8 35 °C
22 °C
Fault
6711
U
Reset HP
No, Yes
No
Service / special operation
7141
U
Emergency operation
Off, On
Off
Off: Heat pump functions normally (with boosters if necessary).
On: Heat pump uses the electric boost system or the boiler connection
Use the “On” position only in Assist mode or Test mode: may result in high power bills
Diagnostics heat generation
8410
U
Return temperature HP
0 140 °C
--
Setpoint (flow) HP
--
8412
U
Flow temperature HP
0 140 °C
--
Setpoint (flow) HP
--
8427
U
Source inlet temperature
-50 50 °C
--
8429
U
Source outlet temperature
-50 50 °C
--
Diagnostics consumers
8700
U
Outdoor temperature
-50 50 °C
--
8701
U
Outdoor temperature mini
Reset ? (no, yes)
-50 50 °C
--
8702
U
Outdoor temperature max
Reset ? (no, yes)
-50 50 °C
--
8740
U
Room temperature 1
0 50 °C
--
Room setpoint 1
20 °C
8743
U
Flow temperature 1
0 140 °C
--
Flow temperature setpoint 1
--
8749
U
Room thermostat 1
No request,
Request
No request
8773
U
Flow temperature 2
0 140 °C
--
Flow temperature setpoint 2
--
8779
U
Room thermostat 2
No request,
Request
No request
8830
U
DHW temperature 1
0 140 °C
--
DHW temperature setpoint
55 °C
8900
U
Temperature pool (B13)
0 140 °C
--
Setpoint pool
24 °C
Operation manual "1639 - EN"
- 21 -
Ground source heat pump atlantic geolia