Line
Function
Setting range
or display
Setting range
or display
Basic
setting
Heating time programme, circuit 1
500
U
Pre-selection (Day / Week)
Mon-Sun, Mon-Fri, Sat-Sun,
Monday, Tuesday, …
Mon-Sun
501
U
1
st
phase On (start)
00:00 --:--
10 min
6:00
502
U
1
st
phase Off (end)
00:00 --:--
10 min
22:00
503
U
2
nd
phase On (start)
00:00 --:--
10 min
--:--
504
U
2
nd
phase Off (end)
00:00 --:--
10 min
--:--
505
U
3
rd
phase On (start)
00:00 --:--
10 min
--:--
506
U
3
rd
phase Off (end)
00:00 --:--
10 min
--:--
516
U
Standard values, Circuit 1
No, Yes
No
Yes + OK: The standard values memorised in the controller replace and cancel the customised heating programmes.
Your customised settings are therefore lost
Heating time programme, circuit 2
Only with the 2nd circuit kit option
520
U
Pre-selection (Day / Week)
Mon-Sun, Mon-Fri, Sat-Sun,
Monday, Tuesday, …
Mon-Sun
521
U
1
st
phase On (start)
00:00 --:--
10 min
6:00
522
U
1
st
phase Off (end)
00:00 --:--
10 min
22:00
523
U
2
nd
phase On (start)
00:00 --:--
10 min
--:--
524
U
2
nd
phase Off (end)
00:00 --:--
10 min
--:--
525
U
3
rd
phase On (start)
00:00 --:--
10 min
--:--
526
U
3
rd
phase Off (end)
00:00 --:--
10 min
--:--
536
U
Standard values, Circuit 2
No, Yes
No
Yes + OK: The standard values memorised in the controller replace and cancel the customised heating programmes.
Your customised settings are therefore lost
Time programme 4 / DHW
If the installation is fitted with the DHW kit.
560
U
Pre-selection (Day / Week)
Mon-Sun, Mon-Fri, Sat-Sun,
Monday, Tuesday, …
Mon-Sun
561
U
1
st
phase On (start)
00:00 --:--
10 min
00:00
562
U
1
st
phase Off (end)
00:00 --:--
10 min
05:00
563
U
2
nd
phase On (start)
00:00 --:--
10 min
14:30
564
U
2
nd
phase Off (end)
00:00 --:--
10 min
17:00
565
U
3
rd
phase On (start)
00:00 --:--
10 min
--:--
566
U
3
rd
phase Off (end)
00:00 --:--
10 min
--:--
576
U
Standard values
No, Yes
No
Yes + OK: The standard values memorised in the controller replace and cancel the customised heating programmes.
Your customised settings are therefore lost