Atlantic 412236 Fitting Instructions Manual Download Page 8

8

5. EXTRACTION FLOW-RATE ADJUSTMENT

This unit is suitable for up to 4 sanitation facilities (each room with a water outlet, except for the kitchen), with 3 bathrooms (or showers) 
at most.
* A washroom is a room with one water outlet, but without bath or shower (cellar, laundry room, toilet with washbasin, etc.).

5.2. Washroom flow rate settings

 

REGULATORY AIRFLOWS EXPRESSED IN m³/h

Number of principal 

rooms in the dwelling

Kitchen

Bathroom or shower room, 

including a toilet cubicle

Another 

washroom*

Toilet cubicle

Single

Multiple

2
3
4

5 and more

90

105
120
135

15
30
30
30

15
15
30
30

15
15
30
30

15
15
15
15

Check the terphane flap is in the correct position in the WC connection.

Identification of connection 
"SDB" (30 m³/h)

Identification of connection 
"WC" (15 m³/h)

Correct position

(Section view)

Wrong position

(Section view)

If the flap is in the wrong position, put it in 

the correct one (Section view)

Replace the 
flap in its 
housing up to 
the "clip"

Flap for 

regulation

Flap for 

regulation

5.1. Extraction flow-rate adjustment

Regulatory air flows:

Balancing flow rates:
If a significant divergence is found between the flow rate in and the flow rate out, balance it using a manual register RR125 (see p. 9).

Summary of Contents for 412236

Page 1: ...FITTING INSTRUCTIONS PRIMOCOSY HR BP HR SRI BP 412236 412237 Family 4 N 4126 Issue Date 02 2017 ...

Page 2: ...3 3 Connection of air flow associated terminals 6 4 ELECTRIC CABLING 7 5 EXTRACTION FLOW RATE ADJUSTMENT 8 5 1 Extraction flow rate adjustment 8 5 2 Washroom flow rate settings 8 6 BY PASS PRINCIPLE 9 7 ACCESSORIES NOT SUPPLIED 9 8 ANNUAL MAINTENANCE 10 8 1 Filter clogging indicator 10 8 2 Changing filters 10 8 3 Maintenance of exchanger and motorised fans 11 9 WARRANTY 12 10 PROTECTING THE ENVIRO...

Page 3: ...ards 2 DESCRIPTION 2 1 General points Dual flow control unit for private house from T2 to T7 with a maximum of 4 washrooms Horizontal installation in roofspace ideal for renovation and replacement of existing products Primocosy HR HR SRI High performance heat exchanger BY PASS function for the exchange to bring cool air in during summer nights Individual room airflow controls with regulators in th...

Page 4: ...igh speed versions For SRI 23 hr low speed versions and 1hr high speed versions 2 5 Dimensions Current Power consumption Weighted power PV GV PV GV PRIMOCOSY HR 0 4A 0 6A 40W 122W 47 1 W th C PRIMOCOSY HR SRI 0 4A 0 6A 40W 122W 43 7 W th C 4 9 0 700 300 Ø125 Ø125 3 X Ø80 Ø125 Ø80 70 700 70 Ø125 Fixed plate 70 490 70 ...

Page 5: ...ed under the product after installation Check the sealing of the whole assembly and the run off of the condensates WARNING Check the discharge pipe never rises above the level of the condensates connector For easier maintenance leave a 300mm space above and behind the appliance 3 cm or 5 Condensates connection OK NOK Note Condensates connection has a built in siphon There is no need to install ano...

Page 6: ...hrooms Ø80 Kitchen connection with regulator X 1 X 3 Fresh air inlet Used air outlet Fresh air blowing Washroom extraction Kitchen extraction To prevent unwanted load losses it is vital to avoid unnecessary elbow joints to extend straight sections without pulling not to crush the conduits to limit the length of the conduits to plug unwanted outlets with the plugs supplied Example of system with di...

Page 7: ...er clip into the hole to do a reset See the SRI remote control manual for the parameters PRIMOCOSY HR SRI BP BROWN PHASE EARTH NEUTRAL CASING CABLE FACTORY WIRING INSTALLER WIRING BLUE OR GREY 230V POWER SUPPLY 4 ELECTRIC CABLING RESET access This equipment must be installed by suitably qualified persons The installation must comply with NF C 15 100 and with professional standards Each product or ...

Page 8: ... cubicle Single Multiple 2 3 4 5 and more 90 105 120 135 15 30 30 30 15 15 30 30 15 15 30 30 15 15 15 15 Check the terphane flap is in the correct position in the WC connection Identification of connection SDB 30 m h Identification of connection WC 15 m h Correct position Section view Wrong position Section view If the flap is in the wrong position put it in the correct one Section view Replace th...

Page 9: ...ne fois le réseau installé il est né cessaire de régler les bouches d insuffl ation ai équiréparti dans toutes les pièces Pour cela ouvrir toutes les bouches du réseau C la plus éloignée de la centrale véri fier qu il y a un débit minimum Ensuite passer quelques tours puis répéter l opération sur toutes les bouches d insufflat ion en le au fur et à mesure que l on se rapproche de la centrale Warm ...

Page 10: ...d les changer Filtres disponibles sur la boutique Atlantic MODE D EMPLOI 1 Appuyer pour enclencher la pastille 2 Lorsque le témoin rouge atteint réf 412190 INDICATEUR DE CHANGEMENT DE FILTRES VMC www boutique atlantic fr Avec cette carte suivez l usure quand les changer Filtres disponibles sur la boutique Atlantic When the indicator is full change the filters A new indicator is supplied with repla...

Page 11: ...the right way round taking care the closure hooks are properly in place Screw up the 4 crosshead screws Pull out the motorised fan units to dust them with a dry brush Motorised fan unit Disconnect the terminal strip before removing the BY PASS exchanger assembly Grasp at the sides and pull out upwards Carefully clean the exchanger using a domestic vacuum cleaner DO NOT USE LIQUID OF ANY KIND WHETH...

Page 12: ...nce is guaranteed against all manufacturing faults for two years from the date of purchase For this ATLANTIC Climatisation et Ventilation offers exchange or supply of parts found to be defective after inspection by its after sales service In no case may the warranty cover additional costs such as labour transport or compensation of any kind The warranty does not cover damage caused by installation...

Reviews: