3. INSTALLATION
3.2. Casing installation
Attach the condensate discharge connector (on the product) to the waste water system (Ø16 int. pipe not supplied) using the clamping
sleeve. The appliance must be fitted with a 3cm or 5% gradient so that the condensates flow off naturally.
The condensate discharge
pipe and the connector must be insulated to prevent freezing.
Check the connector is properly fitted under the product after installation.
Check the sealing of the whole assembly, and the run-off of the condensates.
WARNING: Check the discharge pipe never rises above the level of the condensates connector.
For easier maintenance, leave a 300mm space above and behind the appliance.
3 cm or 5%
Condensates connection
OK
NOK
Note: Condensates connection has a built-in siphon. There is no need to install another
siphon on the outlet.
Do not dismantle moving parts to install connection points.
SEAL THE FITTING IN THE PIPE
USING THE CLAMPING SLEEVE
4
in reverse
+ 1/4 OF A TURN
3.1. Fitting connection points