I. Product overview 

 

ATL-930  Addressable  smoke  detector  (Detector  hereunder)  is  a  kind  of  photoelectric  smoke  detector. 
With an internal microprocessor, it supports electronic coding and is accessed through a compatible fire 
alarm control panel of ATL-MN300 via a two-wire bus. The detector realizes real-time acquisition of the 
in situ smoke concentration data and sends back the data to a fire alarm control 
panel. It can also receive and execute the control commands given by a fire alarm 
control panel. 
The  detector  is  suitable  for  such  industrial  and  civil  buildings  that  have  a  great 
deal  of  smoke  during  fires  but  no  smoke  under  normal  circumstances,  such  as 
restaurants,  hotels,  teaching  buildings,  office  buildings,  computer  rooms, 
communication  machine  rooms,  libraries  and  archives.  It  is  not  suitable  for   
places  with  a  great  deal  of  retained  dust  and  water  mist,  places  where  steam 
and/or oil mist may be generated and places with  retained smoke under normal 
circumstances.   

II. Product features 

 

It can realize electronic coding and rewrite the address via coder in situ. 

 

Within  a  single-chip  microcomputer,  it  can  process  the  sampling  data  in  real-time,  save  the 

latest 144 historical data and realize a curve tracing for the field situation. 

 

It has a temperature, humidity and dust accumulation drift compensation function and a sensor 

fault detection function (fault reporting to fire alarm control panel).   

 

Non-polarity, two-bus connection that ensures convenient installation and maintenance.   

 

Designed with an upper cover and a lower cover and installed on an independent base, it can 

be installed, debugged and maintained conveniently.   

III. Technical parameters 

1.

 

Executive standard: GB4715-2005 

2.

 

Operating voltage: 24V (pulse modulation) 

3.

 

Operating current: 

300uA (monitoring status) or 

1.5mA (alarm status) 

4.

 

Work indication: The red indicator will blink in the monitoring status or remain lit in the alarm 

status. 

5.

 

Weight: about 70g 

6.

 

External dimensions: diameter: 100mm, height: 55mm (with the base) 

7.

 

Wiring method: non-polarity two-bus system (L1, L2) 

8.

 

Operating environment: Indoor, temperature: 

10

℃~

+55

; relative humidity: 

95% (40

±

2

, without condensation) 

9.

 

Coding mode: It can realize electronic coding via coder in situ. Address codes 1 to 324 are 

available for selection. 

10.

  Installation height: 

12m 

11.

  Protection  area:  about  60m

2

.  For  details,  see  related  provisions  in  GB50116-98 

Code  for 

Design of Automatic Fire Alarm System

 

12.

    Matched host machine: fire alarm control panel (such as ATL-MN300)

 