9/12 

 

Frequency

: Standard 50 Hz if not otherwise stated in the type label. 

Fuse protection

: The supply has a fuse with a breaking capacity of at least 1500 A. 

Earth Leakage Circuit Breaker (ELCB

): It is recommended to use a supply with 30 mA ELCB. 

Please observe the type label for further data. Luminaires for 110 VAC or 230 VAC supply are to 
be connected to a supply incorporating protective earth conductor. 

3.7  Adding accessories to SLAM Star 

Atexor  provides  a  number  of  different  accessories  but  in  case  you  afterwards  want  to  add 
accessories of your own for the SLAM Star unit, please note the following points: 

1.  The  user  is  fully  responsible  for  the  use  of  the  equipment  including  service  and 

maintenance 

2.  In case of adding accessories the following is mandatory 

a.  The construction of the certified unit shall not change 
b.  The IP class of the unit shall not decrease 

3.  The static electricity is taken account (e.g. electrostatic bonding) 

In  case  you  do  not  want  to  do  your  own  risk  assessment  for  the  accessories  please  view 
the whole range of accessories at 

www.atexor.com

 

3.8  Linking luminaires in series 

SLAM Star units may be equipped with Ex-certified socket in the factory. Sockets are considered 
optional so they are added to the unit upon customer’s special request. 

In-built  sockets  are  recommended  when  the  illuminated  area  is  notably  large,  complex  or  not 
enough  wiring  points  are  available.  Linking  the  units  in  series  save  time,  amount  of  cable  and 
provide an opportunity to build a chain of lights to provide enough illumination. 

When linking the units together, please observe the following 

1)  Connect the first luminaire to the power supply and then connect the other luminaries to 

each other one by one 

2)  The in-built sockets are only for chaining Atexor SLAM products 
3)  Amount of luminaires that may be connected with each other depends on the supply 

voltage 

4)  The total length of the light chain does not exceed 66 meters 
5)  The total current of the electrical installation does not exceed 16 A 
6)  Competent person of the operator shall control and accept the temporary electrical 

installation at the site 

General guide for linking SLAM Star luminaires with 5 m 3x1,5 mm

2

 (or 3x2,5 mm

2

) cable: 

Supply 

voltage 

Type of luminaire 

Amount of 
luminaires

 

230 V 

SLAM Star 

110 V 

SLAM Star 

42 V 

SLAM Star 

24 V 

SLAM Star 

If you want to link SLAM Star with other SLAM luminaires, contact sales for further information. 

Summary of Contents for SLAM Star

Page 1: ...Instructions for Safe Use Star Certification N o VTT 15 ATEX 077X and IECEx by VTT Thank you for choosing SLAM Star portable work light for your job site Purpose of this manual is to provide you all...

Page 2: ...e with Equipment group IIA IIB or IIC 6 2 5 Temperature class of the equipment 6 2 6 Environmental criteria 7 3 Operating instructions 8 3 1 Personnel 8 3 2 Storage 8 3 3 Before first use 8 3 4 Visual...

Page 3: ...ndependent from each others Under failure of one control gear the others still continue operating Low voltage protection smart feature brings reliability and convenience for use especially when operat...

Page 4: ...losion hazardous areas II Certified for use in areas excluding mines 2 Equipment category suitable for Zone 1 and Zone 2 G Certification taking account explosion hazardous GASES Explanation of marking...

Page 5: ...The test report typically specifies the following tests PE resistance test The purpose of this test is to measure persistence of earth conductor Vital test for electrical safety as well as explosion s...

Page 6: ...plosion hazardous areas there are three equipment categories Category 1 product is suitable for use in Zones 0 1 and 2 20 21 and 22 Category 2 product is suitable for use in Zones 1 and 2 21 and 22 Ca...

Page 7: ...on is valid for temperatures between 20 C 40 C If the equipment is used in other temperatures the safety cannot be guaranteed Selection and use of equipment is always under the responsibility of the o...

Page 8: ...LAM Star units are designed to be used together with step down transformers Using SLAM Star unit with transformers of 2 pole socket outlets without grounding bonding imposes certain extra requirements...

Page 9: ...tar units may be equipped with Ex certified socket in the factory Sockets are considered optional so they are added to the unit upon customer s special request In built sockets are recommended when th...

Page 10: ...luminaries to a longer chain than 66 m measured from the protective fuse when the electrical supply is protected with C curve fuse Please refer to local applicable laws and requirements for electrical...

Page 11: ...greater than 100 cm2 the part has to be changed The surface resistance of the transparent parts has to be between 1 M 1 G Please contact Atexor in case you need a simple measuring device which is nee...

Page 12: ...e day Please study at least the following standards EN IEC 60079 14 Electrical installations in hazardous areas EN IEC 60079 10 Classification of hazardous areas EN IEC 60079 17 Inspection and mainten...

Reviews: