13/16
Slam®Hornet luminaires with LED modules:
Supply
voltage
I
MAX
=16 A
Recommended
max. Load
(max.80 %)
Cable length
Type of luminary
Theoretical
number of
luminaries in
series
230 V
2900 W
5m
CSHLED2 (50
W)
13
110 V
1400 W
5m
CSHLED2 (50
W)
13
42 V
500 W
5m
CSHLED2 (50
W)
10
24 V
300 W
5m
CSHLED2 (50
W)
5
Please note that even if the voltage drop allows certain amount of luminaries to be
linked together, too long chain of luminaries may affect the ability of the fuses in the
electrical input to work properly in a fault situation. Therefore it is not recommended to
chain luminaries to a longer chain than 66m measured from the protective fuse (when
the electrical supply is protected with C-curve fuse). Please refer to local applicable
laws and requirements for electrical installations.
The Slam®Hornet control gear protects itself against excessive voltage drops (numerous
linking) by switching itself off. If too many units are connected to the chain, some units of the
chain will switch off. You may start up by unplugging the last units on the line.
Voltage peaks are more harmful and may damage the control gear permanently when
subjected to excessive peaks continuously.
If fluorescent tubes are flickering when the units are chained up, it may be due to excessive
linking. This may shorten notably the lifetime of fluorescent tube. Unplug the last unit on the
line to ensure proper function of the unit.
4.
Inspection & Maintenance
4.1 After use
Take the following steps after the Slam®Hornet
–unit has been taken out from Ex –area:
1) Clean the unit with a damp cloth (do not use detergents or solvents)
2) Change the anti-static film if only little light comes through it or it is damaged
3) Have a visual check on the unit (condition of cable, PC
–tube, tightness of parts)
4) Let the unit dry in open air