Figure 6: Settings of the configuration switch
7.2
Adjustment of the LED indicator intensity
Depending on a facility where the detectors are installed it is possible to adjust intensity of light indications
emitted by the detector. Such an adjustment is carried out by means of the SW3 switch (see Figure 1).
The way how the detector status and operation mode is indicated in combination with the SW3 switch
position is explained in Section 5.
In case of very high facilities it is recommended to move the switch for the light intensity setting to position
1 (LED – bright/strong).
When facilities are pretty low, for instance boiler rooms, the light intensity SW3 switch should be set to the
position 2 (LED – dimmed/weak).
8
Diagnostics of electrical connections – searching for connection errors
In the case when the detector signals problems with connections (see section 5) the reasons of failure
should be sought using the guidance contained in the table 7.
s. 15|26
User Manual: POD-044-ENG R01
Intermediate
detector
Last detector
Next detectors or
control unit