Product Features
301
© 2017, ATEÏS, member of PAX ProAV Group
The CD-16 remote paging console which serves up to eight zones individually with an All-Call option.
Zone selection buttons and Fireman microphone are encased in a heavy-duty IP30 wall-mounted metal
box with a lockable door.
The CD-16 console use the same architecture as the PPM paging console, with a junction box embedded
into the enclosure multiple units (only the first console in the chain is under monitored). The zone buttons
of CD-16 represent a single zone or group of zones and can be easily programmed through the system
GUI using “drag and drop” functionality. The Push- To-Talk button can be programmed for PTT or
latching operation. The status indicators including Power, EVAC and Fault which show the status of all the
zone are also provided with.
The maximum distance between units is up to 300M. The CD-16 is powered over RS485 via CAT-5 (FTP/
STP), however if power is not available over RS485 it can be locally powered by using a 24V DC supply.
In case connecting 4 CD8 units on the 4 set of PDC port at the same, external power supply may be
required).
There are two versions of the CD-16 paging console with identical hardware and functionality but
different firmware for compatibility with different systems.
CD-16-AS: For IDA8 system and ECS system controllers and slaves. (The CD-16 is function and
connect to per PDC port. In case connecting 4 CD16 units on the 4 set of PDC port at the same,
external power supply may be required).
CD-16-G2: For DIVA8 system controllers
.
3.2.15.1 Control Panel
Fireman Microphone Hook
An U-shape hook to place fireman microphone.
Busy Indicator(1~8)
Show the status of zone:
Color
Status
Frequency
Activity
Red
Permanent
Priority of the zone is lower than other sources.
Green
Blinking
°
°
Priority of the zone is higher than other sources.
Green
Permanent
The zone only desired for paging is not using by other
sources.
Fault Indicator
To display fault status of system. Following table list the states of fault: