1
EPND-T-INT-POE
Notice, installation and troubleshooting
ATAL B.V.
Ampèrestraat 35-37
NL-1446 TR PURMEREND
Postbus 783
NL-1440 AT PURMEREND
T
(+31) 0299 630 610
F
(+31) 0299 630 611
E
[email protected]
I
www.atal.nl
Page 1: ... EPND T INT POE Notice installation and troubleshooting ATAL B V Ampèrestraat 35 37 NL 1446 TR PURMEREND Postbus 783 NL 1440 AT PURMEREND T 31 0299 630 610 F 31 0299 630 611 E info atal nl I www atal nl ...
Page 2: ...ocols 19 Website 19 SMTP sending e mails 19 SNMP 19 Modbus TCP 20 SOAP 22 Syslog 24 SNTP 24 Troubleshooting 25 I forgot the device IP address 25 I cannot connect to the device 25 In search window is only IP and MAC address displayed 25 Device IP address is not displayed in window Find device 25 The device is not found even after manually setting MAC address 25 Error or n a is displayed instead the...
Page 3: ...robe TEDX 102E 32 Temperature probe TED 102E 32 Temperature probe TEPD 102C 32 Humidity probe TRHD 101 32 Power supply Adapter EPND AC01 32 Device case holder for RACK 19 ATS AC20 33 Probes holder for RACK 19 ATS AC21 33 CDB WIN database 33 ...
Page 4: ...ervices only by a qualified person The device contains no serviceable parts inside Don t use the device if it doesn t work correctly If you think that the device is not working correctly let check it by qualified service person Don t disassemble the device It s forbidden to use the device without the cover Inside the device can be a dangerous voltage and may be risk of electric shock Use only the ...
Page 5: ...to Syslog server The device setup can be made by the TSensor software or web interface TSensor software can be free downloaded from the manufacturer s website Also you will find there latest firmware for your device Do not upload to your device firmware which is not designed for it Unsupported firmware can damage your device If you want to use PoE you must use PoE switch compatible with IEEE 802 3...
Page 6: ...te cable free IP address in your network for Web Sensor EPND 4S POE up to 4 temperatures probes type TEDX 102E TED 102E TEPD 102C or relative humidity probe TRHD 101 Web Sensor EPND 3T POE supports up to 3 probes Mounting the device check if the equipment from previous chapter are available install the latest version of TSensor software This software is used to all device settings TSensor software...
Page 7: ...ording to information from the previous point When you installing several new devices connect them to the network one after another connect probes to Web Sensor EPND 3T POE or Web Sensor EPND 4S POE connect the Ethernet connector if the power over Ethernet PoE is not used connect the power adapter 5V 250mA LEDs on LAN connector should blink after connecting the power Web Sensor EPND T INT POE conn...
Page 8: ...ctions If your device is not listed then click Help My device wasn t found Then follow the instructions MAC address is on product label The device is factory set to IP 192 168 1 213 gateway may not be entered if you want to use the device only in local network If you set the same IP address which is already used the device will not work correctly and there will be collisions on the network If the ...
Page 9: ...etc Settings are saved after click on button Save changes Checking functions The last step is to check measured values on the device website In the address bar of the web browser enter the device IP address If the default IP address was not changed then insert http 192 168 1 213 Displayed web page lists actual measured values If the web pages are disabled you can see text Access denied If the meas...
Page 10: ...setup using web interface or TSensor software Web interface can be managed by the web browser Main page will be shown when you insert device address into address bar of your web browser There you find actual measured values Page with history graphs is shown when you click to tile with actual values Access to device setup is possible via tile Settings Chapter 3 ...
Page 11: ... server using option Obtain an IP address automatically Static IP address is configurable via field IP address It is not necessary setup Default gateway while you use device inside one subnet only DNS server IP is required to set for proper function of DNS Option Standard subnet mask sets network mask automatically according A B or C network class Subnet mask field must be set manually when networ...
Page 12: ...set In Point 3 the temperature has risen over limit again During the time delay the value does not drop below the set limit and therefore was in Point 4 caused alarm At this moment were sent e mails traps and set alarm flag on website SNMP and Modbus The alarm lasted up to Point 5 when the temperature dropped below the set hysteresis temperature limit hysteresis At this moment was active alarm cle...
Page 13: ...arching for connected probes All changes must be confirmed using Apply settings button History values are cleared after changing of channel settings SOAP protocol SOAP protocol can be enabled by option SOAP protocol enabled Destination SOAP server can be set via SOAP server address For setup of server port can be used option SOAP server port Device sends SOAP message according selected Sending int...
Page 14: ...cation Into fields Recipient 1 to Recipient 3 it is possible set address of email recipients Option Short email enable sending emails in short format This format is usable when you need to forward emails into SMS messages When option Alarm email repeat sending interval is enabled and there is active alarm on channel then emails with actual values are sent repeatedly Info email sending interval opt...
Page 15: ...log server IP address SNMP For reading values via SNMP it is necessary to know password SNMP read community SNMP Trap can be delivered up to three IP address IP address of the Trap recipient SNMP Traps are sent at alarm or error state on the channel Trap feature can be enabled by option Trap enabled Time Time synchronization with SNTP server can be enabled by Time synchronization enabled option IP...
Page 16: ...y to set administrator password This password will be required for device settings When secured access is required even to actual values reading it is possible to enable User account only for viewing Port of the www server can be changed from the default value 80 using filed WWW port Web pages with actual values are refreshed according to Web refresh interval field Setup using TSensor software TSe...
Page 17: ...bes At TRHD 101 humidity probe is possible set correction of the humidity and temperature Factory defaults Factory defaults button set the device into factory configuration Network parameters IP address Subnet mask Gateway DNS are left without changes Network parameters are changed while you press button at left side of device during power supply connection Factory defaults have no effect to user ...
Page 18: ...er password cleared Modbus TCP protocol port 502 Modbus TCP enabled yes History storage interval sec 60 SOAP message when alarm occurs yes SOAP destination port 80 SOAP server address cleared SOAP sending interval sec 60 SOAP protocol enabled off Syslog server IP address 0 0 0 0 Syslog protocol enabled off SNTP server IP address 0 0 0 0 GMT offset min 0 NTP synchronization every hour off SNTP sync...
Page 19: ...te SMTP sending e mails When measured values are over the set limits the device allows send e mail to a maximum of 3 addresses E mail is send when alarm condition on the channel is cleared or a measuring error occurs It is possible to set repeat interval for email sending For correct sending of e mails it is necessary to set address of SMTP server Domain address can be used as SMTP server address ...
Page 20: ...urred a warning messages trap can be sent to selected IP addresses Addresses can be set using TSensor software or web interface Traps are sent via UDP protocol on port 162 The device can send following traps Trap Description 0 0 Reset of the device 1 0 Settings was changed 6 0 Testing Trap 6 1 NTP synchronization error 6 2 E mail sending error SMTP server login error 6 3 SMTP authentication error ...
Page 21: ...emperature Int 10 40001 0x9C41 Channel 1 alarm status Ascii 40002 0x9C42 Channel 1 upper limit Int 10 40003 0x9C43 Channel 1 lower limit Int 10 40004 0x9C44 Channel 1 hysteresis Int 10 40005 0x9C45 Channel 1 delay uInt 40006 0x9C46 Channel 2 temperature Int 10 40007 0x9C47 Channel 2 alarm status Ascii 40008 0x9C48 Channel 2 upper limit Int 10 40009 0x9C49 Channel 2 lower limit Int 10 40010 0x9C4A ...
Page 22: ...message example Host 192 168 1 132 Content Type text xml charset utf 8 Content Length 751 SOAPAction http tempuri org InsertP8xxxSample xml version 1 0 encoding utf 8 soap Envelope xmlns soap http schemas xmlsoap org soap envelope xmlns xsi http www w3 org 2001 XMLSchema instance xmlns xsd http www w3 org 2001 XMLSchema soap Body InsertP8xxxSample xmlns http cometsystem cz schemas soapP8xxx xsd na...
Page 23: ...from Web Sensor P86xx Example uses Apache 2 2 10 web server and PHP 5 2 6 It is required to install and enable SOAP extension for PHP This example store incoming messages to the hard drive function InsertP8xxxSample name sn tmr kind c1 c2 c3 c4 c5 val1 NULL val2 NULL val3 NULL val4 NULL if c1 e 1 val1 c1 v if c2 e 1 val2 c2 v if c3 e 1 val3 c3 v if c4 e 1 val4 c4 v data Time StrFTime y m d H M S T...
Page 24: ...OAP file not found SOAP message sending error SOAP host error SOAP sock error SOAP delivery error SOAP dns error High alarm CHx Upper alarm on channel Low alarm CHx Lower alarm on channel Clearing CHx Clearing alarm on channel Error CHx Measuring error SNTP The device allows time synchronization with NTP SNTP server SNTP protocol version 3 0 is supported RFC1305 Time synchronization is made every ...
Page 25: ...IP address is not displayed in window Find device In TSensor software menu press Help My device was not found in window Find device Follow the software instructions MAC address of the device can be found on product label The device is not found even after manually setting MAC address This problem occurs especially in cases when the IP address of the device belongs to another network and also Subne...
Page 26: ...he password for setup Please reset device to factory defaults Procedure is described at following point Factory defaults This procedure restore device to factory settings including network parameters IP address Subnet mask etc For factory defaults follow these steps disconnect the power supply power adapter or RJ45 connector if PoE is used use something with thin tipped e g paper clip and press th...
Page 27: ...27 Technical specifications Information about technical specifications of the device Dimensions Web Sensor EPND T INT POE Web Sensor EPND 3T POE Chapter 6 ...
Page 28: ... depending on the operating mode Protection IP30 case with electronic Measuring interval 2sec Accuracy EPND T INT POE 0 8 C in temperature range from 10 C to 60 C 2 0 C in temperature range from 10 C to 20 C Accuracy EPND 3T POE and EPND 4S POE depending on used probe e g probe TEPD 102C parameters 0 5 C in temperature range from 10 C to 85 C 2 0 C in temperature range from 10 C to 50 C 2 0 C in t...
Page 29: ...cols TCP IP UDP IP ARP ICMP DHCP TFTP DNS HTTP SMTP SNMPv1 ModbusTCP SNTP SOAPv1 1 Syslog SMTP protocol SMTP authentication AUTH LOGIN Encryption SSL TLS STARTTLS is not supported Supported web browsers Internet Explorer 9 and later Mozilla Firefox 30 and later Google Chrome 36 and later Opera 21 and later Device should be also compatible with other browsers Functionality wasn t tested with other ...
Page 30: ...ND 4S POE 30 C to 80 C Temperature range of probe TED 102E for EPND 3T POE and EPND 4S POE 30 C to 80 C Temperature range of probe TEPD 102C for EPND 3T POE and EPND 4S POE 50 C to 100 C Temperature range of probe TRHD 101 for EPND 3T POE and EPND 4S POE 0 C to 50 C EPND T INT POE working position with sensor cover downwards When mounting in RACK 19 with universal holder ATS AC20 accessories then ...
Page 31: ...ventive maintenance Make sure the cables and probes are not damaged periodically Recommended calibration interval is 2 years Recommended calibration interval for device with humidity probe TRHD 101 is 1 year ...
Page 32: ...h lengths 1 2 5 or 10m Temperature probe TEPD 102C Temperature probe 50 to 100 C with a digital sensor DS18B20 and with Cinch connector for Web Sensor EPND 3T POE and EPND 4S POE Maximum temperature of the probe is 125 C Probe accuracy 0 5 C from 10 to 85 C else 2 C Stainless steel case with length 40mm diameter 5 7mm Stainless steel type 17240 Guaranteed watertight IP67 sensor connected to silico...
Page 33: ...sy mounting probes in RACK 19 CDB WIN database CDB WIN database provide a complex solution for data acquisition alarm monitoring and measured data analyzing from devices Central database server is based on MS SQL technology Client server conception allows to easy and instant access to data Data are accessible from multiple places by the Database Viewer software One license of CDB WIN Database incl...