InControl 3270 and ToConnect 3270

Incedo™ Open Quick Start Brochure 1.0

1

For more information, see:  

Incedo™ Open InControl 3270 / ToConnect 3270 Installation Guide 

Incedo™ Open User Guide

Controller Unit Specifications

Power supply 

17-30 V DC. A UPS solution is recommended

Internal current consumption 

At 27.8 V: 96 mA Max 120 mA

PoE 

PoE+ 30 W IEEE 802.3af/at

Power Out 

12-14 V DC, max 1.6 A (independent of 

power option)

Operating environment 

+5 ° C to +40 ° C, RH 5 % to 95 %

IP class 

44

Dimensions (housing) 

182.3 x 182.3 x 45.5 (W x H x D mm)

Maximum number of Door 

controllers per Controller 

16

Controller Unit Overview

Hardware components such as electric strikes and readers are 

connected to Controllers and Door controllers on terminal 

blocks. Settings for either controller unit can be made on the 

Mode selection DIP (J), and relay jumper pins (E). The RS-485 

bus is terminated on the terminal block T3 (G).

Controllers are equipped with an additional PCB (M), but the I/O 

connectivity is the same for both controller units.

A) 

RJ-45 Ethernet connector PoE+

B) 

RJ-45 Ethernet connector (no PoE)

C) 

Tamper switch

D) 

Terminal block T1: Analogue inputs and relay outputs

E) 

Relay jumper pins

F) 

Terminal block T2: DC IN, Hi-O, DC OUT

G) 

Terminal block T3: RS-485

H) 

RS-485 termination

I) 

Add-on card connector

J) 

Mode selection DIP

K) 

Label with QR code and MAC Address for Door controller

L) 

Controllers only: Additional PCB with QR code and MAC 

address label for Controller

The MAC address is used to map controller units in the Incedo™ 

Open web application. The (InControl 3270) Controller has two 

separate MAC addresses, since it can act both as a Controller and 

a Door Controller. 

LED Indicators

Controller and Door controller LED reference:

LED Col

Name

On

Blinking

D1

Red

Input IN1

Input is active (triggered)

Sabotage (wire cut)

D2

Red

Input IN2

Input is active (triggered)

Sabotage (wire cut)

D3

Red

Input IN3

Input is active (triggered)

Sabotage (wire cut)

D4

Yellow Relay RE1

Relay is active

n/a

D5

Yellow Relay RE2

Relay is active

n/a

D6

Red

Not used

n/a

n/a

D7

Yellow DC out over-

load

12 V DC output and/or 

onboard relays draw current 

beyond capacity

n/a

D8

Red

Hi-O encrypted Hi-O bus is locked (en-

crypted)

n/a

D9

Green Hi-O unlocked

Hi-O bus is unlocked

n/a

D10 Green RS-485 RX

Data is being received over 

the RS-485 bus

n/a

D11 Red

RS-485 TX

Data is being transmitted 

over the RS-485 bus

n/a

D12 Yellow Voltage 

detected

Voltage between 12-28 V de-

tected on the DC IN terminal 

or the PoE+ port

n/a

D13 Red

Not used

n/a

n/a

D14 Green Network status

Door controller is communi-

cating with the Controller.

IP address received

D15 Blue

Service status

Door controller is not running 

the firmware

Door controller is running 

the firmware

D16 Blue

Controller 

status

n/a

Slow blinking: Controller 

is working, connected 

to cloud. Fast blinking: 

Controller is not connected 

to cloud.

D17 Green Number of 

connected 

devices

n/a

Blinking to indicate number 

of connected devices (Door 

controller or WellCom 

units). One blink per con-

nected device, then a pause 

for 3-4 seconds (repeated).

D18 Red

Number of 

disconnected 

devices

n/a

Blinking to indicate number 

of disconnected devices 

(Door controller or Well-

Com units). One blink per 

disconnected device, then 

a pause for 3-4 seconds 

(repeated).

RE1

RE2

RS-485

DC OUT

Hi-O

DC IN

D10

 

D1

 

D2

 

D3

 

D4

 

D5

 

D6

 

D7

D8

D9

D11

 

D13

 

D12

 

D15

 

D14

 

D16

 

D17

 

D18

 

Warning!

 

Ensure that the controller unit is powered off before 

connecting or disconnecting any wire or cable.