13
EN
The device is equipped with a multi-colour LED with the following meanings:
Standard version
LED
Status
Function
Green
Flashes 1:1
Switching procedure
Illuminates
Normal mode
Error messages
LED
Status
Function
Red
Illuminates
Fire/fire detection
Illuminates
(approx. 4
seconds)
Locking element/freely operating door closer switched
off for this period.
(Inspection button or manual triggering button will be
actuated)
Illuminates
External smoke switch connected
Cable break on smoke switch
Flashes 1:1
Short circuit (locking element output), locking ele-
ment inactive.
Inspect the system completely for the triggering func-
tion after remedying the short circuit.
Yellow
Flashes
Soiling (limiting value nearly reached)
Smoke switch must be exchanged.
Locking remains active until the limit value is exceeded
(LED display switches over to RED)
Illuminates
External smoke switch connected
Incorrect configuration of the smoke switch / cable
monitoring
Inspect plug-in bridge J2 (red) / resistors in external
smoke switch
Illuminates
Manual triggering button connected
Cable monitoring
Remove plug-in bridge J1 (black) / inspect resistors in
manual trigger
I
I
Display
Summary of Contents for DC700G-FMS-K
Page 9: ...9 DE Gewährleistung Entsorgung ...
Page 17: ...17 EN ...
Page 25: ...25 FR ...
Page 33: ...33 NL ...
Page 34: ......