![Asentria Teleboss 850 User Manual Download Page 45](http://html.mh-extra.com/html/asentria/teleboss-850/teleboss-850_user-manual_2981745045.webp)
TeleBoss 850 2.06.280_STD User Manual
Page 39
TeleBoss 850 - Additional Authentication Options
A) Secure Authentication via Telnet [OFF]
B) For Telnet, Send Password To []
C) Secure Authentication via Modem [OFF]
D) For Modem, Send Password To []
E) Secure Authentication via Local Command Port [OFF]
F) Password Expires After [30]
G) Secure Callback 1 []
H) Secure Callback 2 []
I) Secure Callback 3 []
Secure Authentication via Telnet/Modem
toggles between OFF (regular), CHALLENGE, and SEND PASSWORD
authentication modes. Default setting for each is OFF.
OFF (regular) authentication requires only the normal username/password authentication.
CHALLENGE requires the user send their username/password and then they are prompted with a short challenge
code. That code must be plugged into a program called Response Code Generator (RCG). This software can be
found on the Documentation and Utilities CD. Contact Asentria for more information on how to use or obtain this
application. RCG requires a shared secret as well as the challenge code generated by the T850. The user must
then respond with the proper hash generated by RCG in order to gain access.
SEND PASSWORD will generate a single-use password and send it to the Email address(es) specified by the
next option. That password will only allow a login for the user whom it was generated for.
For Telnet/Modem, Send Password To
sets the Email address(es) where the single-use password is to be sent.
Secure Authentication via Local Command Port
toggles between OFF (regular), and CHALLENGE. Because the
user is connected via the local Console port, Send Password is not an option. Default setting is OFF.
Password Expires After
sets the number of minutes (0
– 180) before the single-use password expires. A setting of 0
means the password will never automatically expire. Default setting is 0.
Secure Callback
n
sets the modem callback numbers. If configured, the T850 will disconnect any modem
connections from this user and then attempt to dial out to each of these numbers. If one of the numbers answers, the
other end must respond with the login credentials of the user used to initiate the callback. (Max length 48 chars)
Authentication Settings
TeleBoss 850 - Authentication Settings
A) Local Command Requires Password [OFF]
B) Modem Callin Requires Password [OFF]
C) TCP/IP Port 23 Requires Password [ON]
D) TCP/IP Port 210x Requires Password [OFF]
E) TCP/IP Port 220x Requires Password [OFF]
F) Username and/or Password Required [PASSWORD ONLY]
G) Shared Secret for Challenge/Response []
Authentication Settings set parameters for passwords and security that are required for
every
user who attempts to
log into the T850.
Local Command Requires Password
is an ON/OFF toggle to set whether a password for I/O2 users is required.
Default setting is OFF.
Modem Callin Requires Password
is an ON/OFF toggle to set whether a password for modem users is required.
Default setting is OFF.
TCP/IP Port 23 Requires Password
is an ON/OFF toggle to set whether a password for Telnet (port 23) users is
required. Default setting is ON.
Summary of Contents for Teleboss 850
Page 6: ......