Alarm Trap Number / Return to Normal Trap Number
These options set the number to be sent with any SNMP traps for this event. The default is 511, but the
trap number can also be set in the range of 1000
– 1199 as needed.
Alarm Class / Return to Normal Class
These options are used to set the class for the alarm. When one of these options is selected, a list of the
classes previously defined in the
is displayed, from which you can select one to be assigned
to this event.
CPE Alarm Settings (Ping Alarms) as accessed via Web UI
On the Web Interface the CPE settings are called Ping Alarms. All of the settings to configure Ping Alarms
can be access from the Device Management Page.
The Event settings as covered in the previous section are in the upper section of the page. The Device
settings as described in the Network Settings/
section are located in the lower section of the
page. On the Web Interface the two menus are conveniently located on the same page.
Reset Event Settings
The Reset Event Settings are used to configure event actions to be performed after the unit has been
restarted. These actions would be executed regardless of whether the unit was reset via a restart
command or by power cycling.
TeleBoss 830 - Reset Event Settings
A) Enable Event [OFF]
B) Event Actions []
C) Event Message [Reset Event]
D) Event Class [Info]
E) Event Trap Number [543]
F) Delay After Reset (seconds) [0]
Enable Event
This is an ON/OFF toggle to enable the Reset Event. The default setting is OFF.