Ascon Tecnologic - K31D - OPERATING INSTRUCTIONS - PAG. 9

the instrument shows 

noAt

 on the display.

In case of probe error, the instrument automatically stops the 
cycle in progress.
The values calculated by Auto-tuning are automatically 
stored in the instrument memory at the end of the correct 
PID parameters tuning.

5.8.2 

How to activate Self-tuning function

Program and activate the desired Set Point;

Set parameter 

Cont

 = 

Pid

;

If Single Action control, set parameter 

Func

 according to 

the process to be controlled through output 

1.rEG

;

Program an output as 

2.rEG

 if the instrument controls the 

plant with 

double action 

or a

 time positioning servodrive

;

Set parameter 

SELF

 = 

yES

;

Exit from the parameter programming;

Connect the instrument to the controlled plant;

Activate Self-tuning selecting the entry 

tunE

 in the main 

menu (or using the 

 key, when correctly programmed) .

When the Self-tuning function is active, the LED 

Tun

 is per-

manently lit up and all the PID parameters (

Pb

Int

dEr

,

etc.) 

are no longer displayed

.

To stop the Auto-tuning cycle or deactivate the Self-tuning 
function select a different control type: 

rEG

oPLo

 or 

oFF

 

from the menu 

SEL

.  If the instrument is switched OFF during 

Auto-tuning or with the Self-tuning function activated, these 
functions will remain activated the next time it is switched ON.

5.9  Dynamic Set Point change and automatic 

switching between two Set Points

  

(ramps an dwell time)

All parameters referring to the ramps functioning are con-
tained in the group 

]

rEG

.

It is possible to reach the Set Point in a predetermined time 
(in any case longer than the time the plant would naturally 
need).  This could be useful in those processes (heating 
or chemical treatments, etc.) where the Set Point must be 
reached gradually or in a predetermined time.
Once the instrument has 

reached

 the

 first Set Point

 (

SP1

) it 

is possible to 

switch

 automatically to the 

second Set Point

 

(

SP2

after a set time

, thus obtaining a simple automatic pro-

cess cycle.  These functions are available for all the program-
mable controls (PID single and double action, ON/OFF and 
Neutral Zone ON/OFF).
The function is determined by the following parameters:

SLor

  Gradient of first ramp expressed in unit/minute;

SLoF

  Gradient of second ramp expressed in unit/minute;

dur.t

  Dwell time of 

SP1

 Set Point before automatic switching 

to 

SP2

 Set Point (expressed in hours and minutes).

The functions are deactivated when the relative parameters 
are set to 

InF

.

If is desired only one ramp (e.g. to reach 

SP1

) it is enough to 

program the parameter 

SLor

 with the desired value.

The ramp 

SLor

 will always be 

active

 at 

Power ON

 and 

when the 

Active Set Point value is changed

.

On the contrary, if an 

automatic cycle

 is to be executed at 

Power ON

, program 

nSP

 = 

2

, then the two Set Point values 

SP1

 and 

SP2

 and naturally parameters 

SLor

dur.t

 and 

SLoF

 with the desired values.

In this case at the end of the cycle all the ramps would not 
be more active.

PV

SP1

SP1

time [min]

SLor

SLor

Change SP1 Value

Auto Change Set Point

PV

SP1
SP2

time [min]

dur.t

SLor

SLoF

Examples with starts from values lower than SP1 and with 
decreasing of the Set Point.

Note: 

In case of PID control, if Auto-tuning is desired whilst 
the ramp function is active, the ramp will not be car-
ried out until the tuning cycle has been completed.   
It is therefore recommended that Auto-tuning be start-
ed avoiding activating the ramp function and, once 
the tuning is finished, deactivate Auto-tuning (

Auto

 = 

oFF

), program the desired ramp and, if it automatic 

tuning is desired, enable the Self-tuning function.

5.10  Soft-start function

All parameters referring to the Soft -Start functioning are 
contained in the group 

]

rEG

.

The 

Soft-Start function

 only works through 

PID control

 

and allows the 

limitation of control power

 when the instru-

ment is 

switched ON

, for a programmable 

period of time

.

This is useful when the actuator, driven by the instrument, 
may be damaged by the excess of power supplied when the 
application is not yet in the normal rating (e.g. for certain 
heating elements).
The function depends on the following parameters:

St.P

  Soft-Start power;

SSt

  Soft-Start time (expressed in hh.mm);

HSEt

  End Soft Start cycle threshold.

If both parameters are programmed with values other than 

OFF

, when Powered ON the instrument gives the output 

power set at parameter 

St.P

 for the time set at 

SSt

 or when 

is reached the absolute value set at 

HSEt

.

Practically, the instrument works in manual condition and 
switches to automatic control at the elapsing of time 

SSt

 or 

when is reached the absolute value programmed at param-
eter 

HSEt

.

To disable the Soft-Start function simply program: 

SSt

 = 

oFF

.

Whenever a measurement error occurs during the Soft-Start 
execution, the function is interrupted and the instrument gives 
the output power programmed at parameter 

oPE

.  If the 

measurement is restored, the Soft-Start remains deactivated.
To activate the Auto-tuning together with Soft-Start set: 

Auto

 = 

4

/

-4

.

Auto-tuning starts automatically at the end of the pro-
grammed Soft-Start cycle.

Summary of Contents for K31D

Page 1: ...an therefore be used in applications that require a control for the temperature difference between 2 different environments such as liquid coolers chillers natural air conditioning systems through the air recirculation heating by solar panels or in many other applications where 2 temperature readings are needed The controller is also Index 1 Instrument description 1 1 1 General description 1 1 2 F...

Page 2: ...that the process value is lower than the one programmed for parameter AdE 12 LED Shift index Indicates that the process value is within the range SP AdE SP AdE 13 LED Shift index Indicates that the process value is higher than the one set for parameter AdE 2 PROGRAMMING 2 1 Set Point Fast Programming This procedure allows you to quickly set the active Set Point and when required the alarm threshol...

Page 3: ...r or disappear on this level by fol lowing this procedure Enter the menu ConF and select the parameter to be made programmable or not programmable in the menu oPEr Once the parameter has been selected if the LED SET is OFF this means that the parameter is programmable only in the menu ConF if instead the SET LED is ON this means that the parameter is also programmable in the menu oPEr To modify th...

Page 4: ...entioned rule must adopt all the necessary protective measures The instrument MUST NOT be used in dangerous environments flammable or explosive without adequate protection The installer must ensure that EMC rules are respected also after the instrument installation if necessary using proper filters 4 INSTALLATION WARNINGS 4 1 Mechanical mounting The instrument in case 78 x 35 mm is designed for fl...

Page 5: ...probe is not connected The instrument allows the measurement calibration that can be used to recalibrate the instrument according to application needs This can be done through parameters OFS1 OFS2 and rot Setting rot 1000 and oFS 1 2 it is possible to set a posi tive or negative offset that is simply added to the value read by the probe before visualisation which remains constant for all the measu...

Page 6: ...2HL the process value considered by the controller is Pr1 P2LL When P2HL and P2LL thresholds are exceeded by Pr2 tem perature a control takes place as if the Pr2 temperature is the value of the limit regardless of the value actually read The aim of this function is to limit the differential regulation to within a maximum range of the Pr2 measurement With the differential control the working mode F...

Page 7: ...gle Action PID control can be obtained by program ming parameter Cont Pid and works on 1 rEG output depend ing on the active Set Point SP the functioning mode Func and on the instrument PID algorithm with 2 freedom degrees If the Out1 analogue output is present 0 4 20 mA 0 2 10 V the output will operate as a regulation output providing a value proportional to the regulation power calculated by the...

Page 8: ...h Func CooL 4 If FAST Auto tuning is desired to start automati cally all times the Set Point is changed or at the end of the programmed Softstart cycle The Auto tuning starts anyway if PV is lower than SP SP 5 with Func HEAt or higher than SP SP 5 with Func CooL 1 If OSCILLATORY Auto tuning is desired to start auto matically all times the instrument is switched ON 2 If OSCILLATORY Auto tuning is d...

Page 9: ...d when the relative parameters are set to InF If is desired only one ramp e g to reach SP1 it is enough to program the parameter SLor with the desired value The ramp SLor will always be active at Power ON and when the Active Set Point value is changed On the contrary if an automatic cycle is to be executed at Power ON program nSP 2 then the two Set Point values SP1 and SP2 and naturally parameters...

Page 10: ...AL1 and is deactivated when thePV goes below the value AL1 HAL1 In this way is possible to program with AL1L and AL1H parameters the minimum and the maximum limits of AL1 thresholds LoAb OUT AL1 AL1 PV HAL1 time HiAb off off off OUT AL1 AL1 PV HAL1 time off off off ON ON ON ON LodE Deviation low alarm The alarm is activated when the process value goes below the value SP AL1 and is deactivated when...

Page 11: ...f a measurement error yES Alarm active no Alarm deactivated 5 12 Loop Break Alarm Function All the parameters referring to the Loop Break alarm function are contained in the group LbA The Loop Break alarm is available on all the instruments which intervenes when for any reason short circuit of a thermocouple thermocouple inversion load interruption the loop control is interrupted First of all it i...

Page 12: ...nSP 2 and when active it disables the selection of the active Set Point through the parameter SPAt and through the key 5 15 RS485 Serial Interface The instrument can be equipped with a RS485 serial com munications interface by means of which it is possible to connect the controller to a network to which other instru ments PLC controllers are connected All these devices typically depend on a Person...

Page 13: ...nfiguration or to keep a copy of the parameters setting of an instrument and allow its rapid retransmission The same device allows to connect a PC via USB with which through the appropriate configuration software for AT Univer salConf tool the operating parameters can be configured To use the A01 device it is necessary that the device or instrument are being supplied AC supply Supply adapter 12 VD...

Page 14: ...Number of decimal figures 0 1 0 12 Aot Analogue control Output type 0 20 0 20mA 4 20 4 20 mA 0 10 0 10 V 2 10 0 10 V 0 10 13 Unit Temperature unit of measurement C F C 14 FiL Input digital filter oFF Not active 0 1 20 0 s 1 0 15 oFS1 Measuring Offset Pr1 1999 9999 0 16 oFS2 Measuring Offset Pr2 1999 9999 0 17 rot Rotation of the measuruing straigìht line 0 000 2 000 1 000 18 InE oPE functioning in...

Page 15: ... 1 33 AL1d AL1 Alarm activation delay oFF Not active 1 9999 s OFF 34 AL1i Alarm AL1 activation in case of probe error no yES no Group AL2 AL2 Alarm Parameters Parameter Description Range Default Note 35 OAL2 Output where alarm AL2 is addressed oFF Not active Out1 Out2 Out3 Out4 oFF 36 PrA2 AL2 Alarm PV reference Pr1 Pr2 P1 2 P1 L Pr1 37 AL2t AL2 Alarm type LoAb Absolute Low HiAb Absolute High LHAb...

Page 16: ... error no yES no Group lba Loop Break Alarm Parameters Parameter Description Range Default Note 55 OLbA Output where LbA alarm is addressed oFF Not active Out1 Out2 Out3 Out4 OFF 56 LbAt Time necessary to activate alarm LbA oFF Not active 0 9999 s OFF Group reg Control Parameters Parameter Description Range Default Note 57 Cont Control type Pid PID on FA Asymmetrical ON OFF on FS Symmetrical ON OF...

Page 17: ...SP Active Set Point selection oFF Control in OFF mode noF 78 diSP Displayed Variable Pr1 Pr1 Value Pr2 Pr2 Value P1 2 Pr1 Pr2 Value Pou Control Power SP F Active Set Point Value SP o Operative Set Point value AL1 AL1 threshold AL2 AL2 threshold AL3 AL3 threshold P1 2 79 AdE Shift value for the shift index functioning 0 OFF 1 9999 2 80 Edit Fast programming Active Set Points and Alarms SE Set Point...

Page 18: ... contact our sales department to obtain authorisation for sending the instru ment to our company The faulty product must be shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of different agreements 8 5 Disposal The appliance or the product must be disposed of separately in compliance with the local standa...

Page 19: ...61010 1 10 HOW TO ORDER Model K31D Instrument with mechanical keys a Power supply H 100 240 VAC L 24 VAC DC F 12 VAC DC b Inputs 2 For PTC NTC Thermistors or Pt1000 resistance thermometer d Output 2 Out2 R Relay SPDT 8A resistive load O Vdc for SSR Not present e Output 3 Out3 R Relay SPST NO 5A resistive load O Vdc for SSR Not present f Output 4 Out4 R Relay SPST NO 5A resistive load O Vdc for SSR...

Page 20: ...Ascon Tecnologic K31D OPERATING INSTRUCTIONS PAG 20 ...

Reviews: